Product data
.
c
Start-up
DALI Manual | 08-2013 | en
72 / 93
Table: Parts list
Pos. Qty Article name
1 1 DALI power supply DALI PS / PS1
2 2 DALI scene controller DALI SC
3 1 DALI group controller DALI GC
4 6 DALI ECG for linear luminaire PCA EXCEL one4all xitec II
5 2 DALI LED control gear for LED downlights LCAI ECO one4all
6 1 DALI emergency control gear for linear luminaire EM PRO
7 1 DALI emergency control gear for emergency sign EM powerLED PRO
Table: Grouping
Conference room
Downlights Group 1
Linear luminaires Group 2
DALI GC Switch position = 1 (Group 1+2):
Group 1 => Switch for downlights
Group 2 => Switch for linear luminaires
Scene assignment
Scenes are called up from two locations. Directly next to the door there is a double switch for switching the light on and
off. The control point next to the screen can also be used to switch the light on and off. In addition, two further
user-defined scenes (e.g. presentation) can be called up.
Control point near door Control point near screen
DALI SC Switch position = 1 (Scenes 1-4):
Scene 1 => Light off
Scene 2 => Light 100 %
Scenes 3 and 4 not wired
Switch position = 1 (Scenes 1-4):
Scene 1 => Light off
Scene 2 => Light 100 %
Scene 3 => Presentation
Scene 4 => Meeting
...