DALI Manual | 08-2013 | en
71 / 93
Sample set-up for a conference room
This section uses the example of the conference room from Chapter 4 to show how a DALI application can be put into
operation with the aid of masterCONFIGURATOR in six easy steps.
The conference room contains 8 DALI luminaires, two DALI SC units, one DALI GC unit and one
DALI Power Supply. The rotary switches on the DALI SC and GC have already been set to the correct position during
installation. The luminaires are connected to the power supply and to the DALI circuit.
Solution with DALI GC and DALI SC
The room is divided into two groups, one for the low-voltage halogen downlights and the other for the linear luminaires.
There are two switching points available.
One by the door for switching the lighting on and off. This is implemented with a DALI SC with the scenes “Lighting on”
and “Lighting off”. The second by the window is implemented with a DALI-SC and a DALI-GC and enables any of four
scenes to be retrieved and both luminaire groups to be individually dimmed.
Figure: Installation for conference room without wiring