Product data
.
c
Designing a DALI application
DALI Manual | 08-2013 | en
68 / 93
Table: Parts list
Pos. Qty Article name
1 1 DALI power supply DALI PS / PS1
2 2 DALI touchpanel DALI TOUCHPANEL 02
3 3 DALI MSensor 02 DALI MSensor 02 (5DPI 41 rc)
4 18 DALI control gear for linear luminaires PCA EXCEL one4all xitec II
Table: DALI checklist
DALI condition Planned / present
Maximum of 64 DALI ECGs 18 DALI devices
Maximum of 16 groups 4 groups
Maximum of 16 scenes
DALI circuit current < Rated power supply current 66 mA
Line length < 300 m (for 1.5mm²) approx. 50 m
5 wires to each luminaire 5 x 1.5mm²
DALI ECG in luminaire Tridonic PCA EXCEL one4all xitec II
Figure: Installation for open-plan office with wiring
Grouping
The luminaires can be grouped in either of two ways. With the DALI RC (see DALI MSensor 02 operating instructions)
or with the masterCONFIGURATOR software (see Reference list).