Product data

.
c
Designing a DALI application
DALI Manual | 08-2013 | en
67 / 93
Open-plan office
Application
Office with 6 workstations plus cabinets.
Each desk has 2 workstations.
Requirement
The lighting consists of 3 rows of luminaires, 2 rows above the workstations and 1 in the walkway and cabinet area.
The requirements for control are as follows:
Figure: Installation for Open-plan office without wiring
Solution with DALI MSensor 02
The room is divided into 4 groups, 3 for the workstation islands and 1 for walkway and cabinet area lighting. The 3
groups for the workstation islands are each controlled with a DALI MSensor 02. The fourth group is controlled with 3
DALI MSensor 02 (increased presence detection area).
Each workstation island and the walkway lighting is independently controlled (presence detection and ambient light
control).
On/off switching via motion sensors
Daylight-dependent control of illuminance
Manual control via DALI TOUCHPANEL