Product data

.
c
Designing a DALI application
DALI Manual | 08-2013 | en
65 / 93
Table: DALI checklist
DALI condition Planned/present
Maximum of 64 DALI ECGs 8 DALI devices
Maximum of 16 groups 2 groups
Maximum of 16 scenes 4 scenes
DALI circuit current < Rated power supply current 34 mA
Line length < 300 m (for 1.5mm²) approx. 20m
5 wires to each luminaire 5 x 1.5mm²
DALI control gear in luminaire Tridonic PCA EXCEL one4all xitec II
Figure: Installation for Conference room with wiring
Grouping
The luminaires can be grouped in either of two ways. With the DALI GC itself or with the masterCONFIGURATOR
configuration software (see Reference list).