Product data

.
c
Designing a DALI application
DALI Manual | 08-2013 | en
63 / 93
Sample applications
Conference room
Application
Conference room for about 10 people
Requirement
The lighting in the room consists of 6 linear luminaires and 2 LED downlights. The requirements for control are as
follows:
Solution with DALI GC and DALI SC
The room is divided into two groups, one for the LED downlights and the other for the linear luminaires.
There are two switching points available.
One by the door for switching the lighting on and off. This is implemented with a DALI SC with the scenes “Lighting on”
and “Lighting off”. The second by the window is implemented with a DALI SC and a DALI GC and enables any of four
scenes to be retrieved and both luminaire groups to be individually dimmed.
The luminaire should be switched and controlled at either of two control points.
There should be a section of different lighting scenarios (e.g. presentation)
The luminaires must be capable of being dimmed