c
DALI sequencer module: DALI SQM
DALI Manual | 08-2013 | en
52 / 93
Set number of scenes in the sequence
Switch off light
The DALI SQM is activated via a floating contact. When the contact is closed the module is active and continually
sends DALI scene calls. The delay time between the scene calls (step time) can be set on a rotary switch on the
module (shortest time 1 second, longest time 30 minutes). A switch on the module allows you to select the scene after
which the sequence starts from the beginning again. The brightness values for the different scenes are set with the
DALI GC and SC or via the masterCONFIGURATOR.
Cross-fade the DALI SQM
Cross-fading from scene to scene is determined by the fade time of the DALI ballasts. The range is from 0.7 seconds
to 90.5 seconds and is set via the masterCONFIGURATOR software. For more information on setting the fade time
please refer to the operating instructions for the masterCONFIGURATOR (see Reference list).
Figure: DALI SQM cross-fade
...
Press UP button to increase number of scenes in the sequence by one
Press DOWN button to decrease number of scenen in the sequence by one
Hold DOWN button down to save number of scenes
I NOTICE
By default 8 scenes are preset. A maximum of 16 scenes can be set.
Hold DOWN button down to switch off the connected luminaires
I NOTICE
If the step time is less than the fade time the next scene will be selected even if the scene has not been completed.