Product data
.
c
DALI multi controller: DALI MC
DALI Manual | 08-2013 | en
38 / 93
10) Stairwell function:
close = command X, start run-on
time, run-on time elapsed =
command Y
If the push-button is pressed, command X is sent and the run-on time starts.
Once the run-on time has elapsed, command Y is sent.
Table: Macro description
Macro Description
Macro 1: Go home Delayed light off (slow fade down)
Macro 2: MSensor
automatic
Lighting control for the selected DALI MSensor is activated
Macro 3:
Sequential scene
recall
The next scene is called up each time button connected to the input is pressed. At the end of
the sequence the process starts again from the beginning.
Macro 4: Dynamic
scene
Pressing the button calls up a sequence of four scenes. The cross-fade time and dwell time
can be freely defined for each scene.
Macro 5:
DALI-Reset
Reset for the defined devices. As an option all the DALI addresses can be deleted
Macro 6: e-Power
ON Level
Sets the Power ON Level of the DALI ballast to the predefined value. DALI devices that do
not support this function ignore the command
Macro 7: PCA
compatibility
Sets the “PCA compatibility” parameter in PCA EXCEL lp devices of generation xitec I to the
predefined value. DALI devices that do not support this function ignore the command
Macro 8:
User-defined DALI
commands
This macro executes a COT file that can be created by the user.
For an explanation of the commands see Appendix / Important DALI parameters and DALI commands.
Default setting
The DALI MC has the following factory default input settings: