• From main panel, run 6-2 with ground to outside disconnect.
• Run 6-2 with ground from outside disconnect to spa.
ALPS SPAS recommends that a 60 AMP 220 GFCI
must be used in disconnect.
• Disconnect must be at least 6 ft. from spa!
Any of the four panels can be drilled out and removed for
easy electrical entry.
• Wire may be drilled thru bottom of spa on wood deck or see page
12 for concrete slab location.
All exposed wire must be INSTALLED IN CONDUIT and have
proper connectors.
ALPS SPAS is not responsible for any mis-wiring of control panel.
All models require a 60 AMP GFCI.
ALUMINUM WIRE WILL VOID WARRANTY!
Swim Spa electrical requirements
From main panel install a 60 AMP GFCI 220 breaker.
Run no# 6-3 with ground. (2 hots, neutral and ground - 4 wires)
Install an outside disconnect (with 60 AMP GFCI Breaker)
No closer than 6 ft from SPA!
Hard wire from disconnect to Swim Spa control panel.