Data Sheet

Product Specification Sheet APS925 - Rev. 08/2016
SDACT-2 Serial Dialer and Digital CommunicatorSDACT-2 Serial Dialer and Digital Communicator
42 Central Drive • Farmingdale • NY • 11735-1202 • Phone: (631) 777-5500 • Fax: (631) 777-559942 Central Drive • Farmingdale • NY • 11735-1202 • Phone: (631) 777-5500 • Fax: (631) 777-5599
TOLL-FREE: (800) 666-4800 • Web: AlphaCommunications.com • Email: info@alphacommunications.comTOLL-FREE: (800) 666-4800 • Web: AlphaCommunications.com • Email: info@alphacommunications.com
Copyrigh1998-2016 Alpha Communications® - All Rights Reserved.
Due to continuous product improvement, all colors, sizes, materials, finishes and specifications are subject to change without notice.
SDACT-2 Shown without the
SDACTBX-GRAY Metal Housing
Architects' And Engineers' SpecificationsArchitects' And Engineers' Specifications
The Serial Dialer Unit unit(s) shall be Alpha Communications® /
Keltron model SDACT-2, or approved equal. The SDACT-2 shall be
used in conjunction with an Alpha Communications® Emergency-
Call (or similar) notification system, to allow alarm indication at an
on- or off-site central station monitoring location.
The SDACT-2 shall have an RS232 port that will allow a string of
RS232 data to be converted to an industry standard SIA format
for alarm event reporting. Unit shall also be provided with 2 SPDT
relays for common alarm and common trouble indication.
The SDACT-2 shall be mountable right to the surface of the wall
when mounted in a the SDACTBX-GRAY junction box cabinet, and
shall require a customer supplied external phone line and jack.
Contractor shall observe all local and national electrical and
building codes.
Supported InterfacesSupported Interfaces
97P1411SD2:
COMP2 protocol @ 9600 baud - data
derived zone number - event code
fixed to Medical Alert (MA)
97P1412SD2:
COMP2 protocol @ 2400 baud -
data derived zone number - event
code fixed to Medical Alert (MA)
97P1413SD2:
COMP2 protocol @ 9600 baud -
data derived zone number - event
code fixed to Burg (BA)
97P1414SD2:
COMP2 protocol @ 9600 baud -
data derived zone and event code
97P1414SD2:
Hybrid protocol @ 9600 baud - data
derived zone number - fixed Medical
Alert (MA) event code or derived Fire
Alarm (FA) event code
SPECIAL INSTALLATION NOTESPECIAL INSTALLATION NOTE
The SDACT-2 serial dialer is typically installed adjacent or
nearby to the AlphaEntry PC Master station. If the SDACT-2
needs to be mounted in a remote location, a distance away
from the USB port on the PC Master, the installer will need to
provide a compatible serial extension cable/device.
SDACT-2 Serial Dialer and Digital CommunicatorSDACT-2 Serial Dialer and Digital Communicator
The Alpha Communications® / Keltron SDACT-2 is a unique
solution that interfaces with emergency-call, access control,
building management and other systems to enable an appropriate
and instantaneous response from personnel at a central or remote
monitoring location. The SDACT-2 provides a bridge to an on- or
off-site central station-style digital receiver through the dial-up
public switched telephone network (PSTN).
The SDACT-2 accepts pre-defined ASCIII RS232 data strings and
converts to SIA, a standard, digital receiver-compatible, alarm
reporting format.
The most common applications for the SDACT-2 is for use with our
AlphaEntry and AlphaEcallemergency-call systems and
devices, although it can be used with other similar systems.
FeaturesFeatures
RS232 Port enables accurate monitoring of event type and
location identification
Test code call-in cycles are programmable. A manual test
button is also included
Transmits signals in industry standard SIA format
Works with a variety of alarm notification equipment
Zones 1-4 supervised EOL, suitable for fault-contact
monitoring
Zones 5-7 are available for loss of AC and battery fail
indications, which are also reported using standard SIA
event codes
Local LEDs and audible devices clearly indicate Serial Dialer
status
SpecificationsSpecifications
Dimensions (in
SDACTBX-GRAY
Housing):
Height: 14.00" (356mm)
Width: 17.00" (432mm)
Depth: 4.00" (102mm) from mounting
surface
Phone Lines:
2 RJ45 receptacles. Line seizure via
RJ31x jack (by others)
Hardwired Zone
Inputs:
7 (4-EOL resistor supervised). EOL
resistor value 10K Ohms.
Audible Device: rated at 92DB
Ringer Equivalence: .1
FCC Reg.# US: KELAL00BSDACT-2
User Controls:
Jumper (8 total) and Pushbuttons:
Reset, Manual Test, Silence, Program.
Power Requirements:
Power Input - regulated or
unregulated, filtered 20.4 to 27.5VDC
Power Draw:
75mA Idle, 200mA all alarm or lamp
test
Programming and
Monitoring Port:
DB-9F RS-232