User`s guide

2. Cabinet Installation
23
164201085 Rev. F0
WARNING: Adhere to all appropriate electrical precautions
CONNECTION PROCEDURE
1. Open the cabinet doors.
2. Install liquid tight conduit to the fitting on the cabinet rear panel and pull the AC primary
wiring into the cabinet housing.
3. Using the receptacle provided, connect the AC high input (black) to the copper
receptacle terminal, the AC neutral input (white) to the silver receptacle terminal, and
the utility protective ground (green) to the green receptacle terminal. The screw tighten
torque is 20 lb in.
4. Position all wiring neatly in the receptacle box and install the receptacle and cover.
5. Using the output wire harness (green and yellow wires with power lock connectors, a
seizure clamp, and a-ring) and cable adapter from the parts kit, install the cable adapter
and ground wire.
Insert the cable adapter from outside the cabinet into the paint-masked hole, along
with supplied cable feed guard bracket for ground mount installation.
Use the locknut to secure the adapter and the large a-ring to the cabinet. Tighten
securely.
6. Install your choice of output cable in the adapter. A right-angle adapter is required for
ground mount installation.
Connect the yellow output wire to the coax cable center conductor by sliding the
seizure clamp into place and tightening securely.
Slide the protective boot over the cable center conductor and seizure clamp. Install
the cable feed guard to the bracket under the cable adapter.
7. Connect an unbroken 6 AWG soft-drawn copper ground wire between the lug provided
on the back of the cabinet and a ground rod for lightning protection. Use a ground rod
clamp of the proper type, above or below grade.
NOTE: If local codes require bonding to utility ground. a separate ground rod
and vertical should be provided. then the two verticals should be bonded
at the bottom of the pole.
2.3 Electrical Connection