2. Cabinet Installation
164201085 Rev. F0
2.2 Ground-Mount Cabinet,
continued
2.2.1 Enclosure Grounding
NOTE: Alpha Technologies recommends using the grounding method illustrated
on the following page. The grounding method for a particular site will be
dependant upon soil type, available space, local codes, NEC (National
Electric Code), and other site-specific characteristics.
NOTE: Alpha Technologies recommends 5 ohms minimum ground resistance
(25
ohms per NEC)
between enclosure and ground rods, in accordance with
IEEE 1100-1999 Powering and grounding Electronic Equipment.
NOTE: Alpha Technologies assumes no responsibility or liability for failure of the
installer to comply with the requirements of all applicable local and national
codes. Where allowed, exothermic welding may be used as an alternative
to Burndy clamps and connectors.