Troubleshooting guide

8
Preface
745-573-B0-001 REV. A
Cautions
NOTE: Enclosure, equipment or parts may be damaged or cause damage if used
or installed improperly.
To avoid damage:
Prior to installation, verify that the AC input voltage to the enclosure and its equipment
match with respect to voltage and frequency.
Prior to installation, verify that the output voltage from the enclosure or its equipment match
the voltage requirements of the connected equipment (load).
Prior to installation, verify that the enclosure’s utility service panel is equipped with a
properly rated circuit breaker for use with the equipment inside. Refer to manufacturer’s
recommendations.
Review and upgrade utility service panel circuit breaker requirements whenever the
equipment within the enclosure is changed.
Prior to installation, contact local utilities, local building maintenance departments, and
cable/piping locator services to ensure that installation does not interfere with existing utility
or building cables/piping.
Do not exceed the output rating of equipment. Verify load requirements prior and during
connection process.
Prior to handling the batteries, touch a grounded metal object to dissipate any static charge
that may have developed on your body.
Alpha Technologies is not responsible for unit damage due to enclosure or installation
temperatures which exceed the operating temperature of the product.
The Lectro CPR UPS is a 36 or 48Vdc system designed for use with either a single or dual
string of three or four 12Vdc batteries. Please refer to Section 3 of this manual for more
details on proper battery installation, maintenance, storage, and replacement procedures
Over current protection and disconnecting means for the AC output are to be supplied by the
electrical installer as required by local electrical codes.
The operating temperature range for the Lectro CPR
®
UPS is –40°C to +55°C for air at the
intake of the CPR module.
CPR UPS installations involving third-party cabinets, not supplied by Lectro or Alpha, require
adequate ventilation, airflow and spacing to ensure that the CPR
®
power supply operates
within a temperature range of -40°C to +55°C. Failure to provide an operating thermal
environment per published specifications will void the warranty.
General Safety Precautions