Troubleshooting guide
8
Preface
745-573-B0-001 REV. A
Cautions
NOTE: Enclosure, equipment or parts may be damaged or cause damage if used
or installed improperly.
To avoid damage:
• Prior to installation, verify that the AC input voltage to the enclosure and its equipment
match with respect to voltage and frequency.
• Prior to installation, verify that the output voltage from the enclosure or its equipment match
the voltage requirements of the connected equipment (load).
• Prior to installation, verify that the enclosure’s utility service panel is equipped with a
properly rated circuit breaker for use with the equipment inside. Refer to manufacturer’s
recommendations.
• Review and upgrade utility service panel circuit breaker requirements whenever the
equipment within the enclosure is changed.
• Prior to installation, contact local utilities, local building maintenance departments, and
cable/piping locator services to ensure that installation does not interfere with existing utility
or building cables/piping.
• Do not exceed the output rating of equipment. Verify load requirements prior and during
connection process.
• Prior to handling the batteries, touch a grounded metal object to dissipate any static charge
that may have developed on your body.
• Alpha Technologies is not responsible for unit damage due to enclosure or installation
temperatures which exceed the operating temperature of the product.
• The Lectro CPR UPS is a 36 or 48Vdc system designed for use with either a single or dual
string of three or four 12Vdc batteries. Please refer to Section 3 of this manual for more
details on proper battery installation, maintenance, storage, and replacement procedures
• Over current protection and disconnecting means for the AC output are to be supplied by the
electrical installer as required by local electrical codes.
• The operating temperature range for the Lectro CPR
®
UPS is –40°C to +55°C for air at the
intake of the CPR module.
• CPR UPS installations involving third-party cabinets, not supplied by Lectro or Alpha, require
adequate ventilation, airflow and spacing to ensure that the CPR
®
power supply operates
within a temperature range of -40°C to +55°C. Failure to provide an operating thermal
environment per published specifications will void the warranty.
General Safety Precautions










