Troubleshooting guide
44
6. Specifications, Continued
745-573-B0-001 REV. A
MODEL
PARAMETER
N om inal Input Voltage
Input Voltage Range (% )
Input Voltage Range
Nom inal Input Curr. (Rest m ode)
Input Frequency
Output Voltage
Output Regulation, 87V Tap
Output Regulation, 75V Tap
Output Regulation, 60V Tap
Output Regulation, 48V Tap
Rated Output Current
120V 36V Extd
Range
230V 36V Euro
(C E )
120V 230V
+30% to -20% +20% to -30%
96 V to 156V 161v to 276V
13A 8A
60Hz, ± 3Hz 50Hz, ± 3Hz
87/75/60 Vrms
(F ie ld S e le c ta b le )
60/48 Vrm s
(F ie ld S e le c ta b le )
± 3% N/A
± 4% N/A
± 4% ± 3%
N/A ± 4%
15A 15A
60Hz, ± 1Hz 50Hz, ± 1HzOutput frequency, Inverter M ode
Waveform
Slew Rate
Crest Ratio (Peak:RMS)
Quasi Squarewave Quasi Squarewave
< 100 Volts/m s < 100 Volts/m s
1.3:1 1.3:1
EFFICIENCY @ 87Vrms ON-LINE REST MODE
@ 100% load
@ 80% load
@ 60% load
@ 40% load
91% 91%
90% 90%
89% 88%
85% 85%
87V Tap % Rated Current
75V Tap % Rated Current
60V Tap % Rated Current
150% N/A
155% N/A
180% 150%
EFFICIENCY @ 87Vrms INVERTER MODE Vdc
@ 100% load
@ 80% load
@ 60% load
@ 40% load
88% 87%
87% 87%
86% 87%
81% 83%
FOLDBACK (NEAR SHORT CIRCUIT CURRENT)
87V Tap
75V Tap
60V Tap
22A N/A
20A N/A
19A 21A
MAX KNEE CURRENT (START UP POWER)
30 sec. on, 30 sec. off > 16.5A > 16.5A
> 110% (3 HOUR CYCLIC OPERATION)
6 sec. on, 26 sec. off > 21A > 21A
SEVERE OVERLOAD (3 HOUR CYCLIC OPERATION)
Operating Range
Humidity
Elevation
-40°C to +55°C at front air inlet
0 to 95% (Non-Condensing)
0 to 10,000 feet (3,000 Meters) above sea
le vel
ENVIRONMENTAL
DC Input Voltage
Constant Current
Constant Voltage
36VDC Nominal
High Charge Rate, threshold at 2.35 VFC
2.35 VFC (M aximum 48 hours)
DC ELECTRICAL
DC Charge Current
Low B a ttery C u toff
6-12A M axim um , depending upon load
< 1.75 VFC
44
745-573-B0-001 REV. A
Table 6-2, 36V Specifications
6.1 Electrical, Mechanical Specifications, Continued