Troubleshooting guide
43
6. Specifications, Continued
745-573-B0-001 REV. A
MODEL
PARAMETER
Nom inal Input Voltage
Input Voltage Range (% )
Input Voltage Range
Nom inal Input Curr. (Rest m ode)
Input Frequency
Output Voltage
Output Regulation, 87V Tap
Output Regulation, 75V Tap
Output Regulation, 60V Tap
Output Regulation, 48V Tap
Rated Output Current
120V Extd Range 220V International 240V (24 A)230V International 23 0V E uro (C E )
120V 220V 230V 230V 240V
+30% to -20% +30% to -30% +30% to -30% +15% to -20% +15% to -20%
96 V to 156V 154V to 286V 161v to 299V 184v to 265V 192V to 276V
13A 7A 7A 6A 11A
60Hz, ± 3Hz 60Hz, ± 3Hz 50Hz, ± 3Hz 50Hz, ± 3Hz 60Hz, ± 3Hz
87/75/60 Vrms
(F ie ld S e le cta b le )
87/75/60 Vrms
(F ie ld S ele cta ble )
87/75/60 Vrms
(F ie ld S e le c ta b le )
60/48 Vrm s
(F ie ld S e le c ta b le )
60/48 Vrm s
(F ield Se lec tab le)
± 3% ± 3% ± 3% N/A ± 3%
± 4% ± 4% ± 4% N/A ± 4%
± 4% ± 4% ± 4% ± 3% ± 4%
N/A N/A N/A ± 3% N/A
15A 15A 15A 15A 24A
60Hz, ± 1Hz 60Hz, ± 1Hz 50Hz, ± 1Hz 50Hz, ± 1Hz 60Hz, ± 1HzOutput frequency, Inverter M ode
Waveform
S lew R ate
Crest Ratio (Peak:RM S)
Quasi Squarewave Quasi Squarewave Quasi Squarewave Quasi Squarewave Quasi Squarewave
< 100 Volts/ms < 100 Volts/m s < 100 Volts/m s < 100 Volts/ms < 100 Volts/ms
1.3:1 1.3:1 1.3:1 1.3:1 1.3:1
EFFICIENCY @ 87Vrms ON-LINE REST MODE
@ 100% load
@ 80% load
@ 60% load
@ 40% load
91% 91% 91% 91% 91%
90% 91% 91% 90% 91%
89% 89% 89% 88% 89%
85% 85% 84% 85% 85%
87V Tap % Rated Current
75V Tap % Rated Current
60V Tap % Rated Current
150% 150% 150% N/A 165%
155% 180% 160% N/A 192%
180% 210% 180% 150% 234%
EFFICIENCY @ 87Vrms INVERTER MODE Vdc
@ 100% load
@ 80% load
@ 60% load
@ 40% load
88% 86% 86% 87% 88%
87% 87% 87% 87% 87%
86% 86% 86% 87% 86%
81% 81% 81% 83% 81%
FOLDBACK (NEAR SHORT CIRCUIT CURRENT)
87V Tap
75V Tap
60V Tap
22A 19A 21A N/A 32A
20A 21A 24A N/A 29A
19A 27A 27A 21A 36A
MAX KNEE CURRENT (START UP POWER)
30 sec. on, 30 sec. off > 16.5A > 16.5A > 16.5A > 16.5A N/A
> 110% (3 HOUR CYCLIC OPERATION)
6 sec. on, 26 sec. off > 21A > 21A > 21A > 21A > 27.25A
SEVERE OVERLOAD (3 HOUR CYCLIC OPERATION)
Operating Range
Humidity
Elevation
-40°C to +55°C at front air inlet of power supply
0 to 95% (Non-Condensing)
0 to 10,000 feet (3,000 M eters) above sea level
ENVIRONMENTAL
DC Input Voltage
Constant Current
Constant Voltage
48VDC Nominal
High Charge Rate, threshold at 2.35 VFC
2.35 VFC (M aximum 48 hours)
DC ELECTRICAL
DC Charge Current
Low B attery C utoff
6-12A M axim um , depending upon load
< 1.75 VFC
Table 6-1, 48V Specifications
6.1 Electrical, Mechanical Specifications