Operator`s manual

164201257 C0
Page 27 6/13/2003
Preliminary
Lectro CPR
®
Operator’s Manual
3.2.2 Connect the red battery cable which comes from the gray connector on the CPR
module to the positive (+) terminal of the left battery. Refer to Figure 3.3-1 for de-
tails. Torque all connections to 60 inch-pounds (6.8 Newton-meters).
3.2.3 Connect the three (3) battery interconnection jumpers as shown in Figure 3.3-1.
Torque all connections to 60 inch-pounds (6.8 Newton-meters).
3.2.4 Confirm that the CPR DC circuit breaker is off (down). Connect the black battery
cable which comes from the gray connector on the CPR module to the negative (-)
terminal of the right battery. Torque connection to 60 inch-pounds (6.8 Newton-
meters).
3.2.5 Measure the DC voltage to ensure proper installation of all battery wiring. Open
circuit DC voltage should measure between 45 volts and 51 volts.
3.2.6 Verify that the gray Anderson connector is properly attached to the left side of the
CPR module.
3.3 Battery Removal
3.3.1 Turn the DC circuit breaker off (down) and observe all precautions for handling
batteries as outlined in Section 3.1.
3.3.2 Remove all batteries in the reverse order of installation.
RED
BLACK
FRONT OF CABINET
Figure 3.3-1: Battery Connections – single string