Operator`s manual
164201257 C0
Page 25 6/13/2003
Preliminary
Lectro CPR
®
Operator’s Manual
Uni t Name
120V Extd Range
220V Internati onal
230V International
230V Euro (CE) 240V (24 A)
Nominal Input Voltage
120V 220V 230V
230V
240V
Input Voltage Range in %
[+30% to -20%]
[+30% to -30%]
[+30% to -30%]
[+15% to -20%] [+15% to -20%]
Input Voltage Range 96V to 156V 154V to 286V 161V to 299V
184V to 265V
192V to 276V
Nominal Input Current (Rest Mode)
13A 7A 7A 8A 11A
Input Frequency
60 Hz, +/- 3Hz
60 Hz, +/- 3Hz 50 Hz, +/- 3Hz 50 Hz, +/- 3Hz 60 Hz, +/- 3Hz
Output Voltage 87/75/60 Vrms
(Field Selectable)
87/75/60 Vrms
(Field Selectable)
87/75/60 Vrms
(Field Selectable)
60/48 Vrms
(Field Selectable)
87/75/60 Vrms
(Field Selectable)
Output Regulation 87 Volt Tap [+/- 3%] [+/- 3%] [+/- 3%] N/A
[+/- 3%]
Output Regulation 75 Volt Tap [+/- 4%]
[+/- 4%]
[+/- 4%] N/A [+/- 4%]
Output Regulation 60 Volt Tap [+/- 4%]
[+/- 4%]
[+/- 4%]
[+/-3%] [+/- 4%]
Output Regulation 48 Volt Tap
N/ A
N/ A
N/ A
[+/-3%] N/A
Rated Output Current
15A
15A
15A15A
24A
Ouptut Frequency(Inverter Mode) 60Hz, +/- 1Hz 60Hz, +/- 1Hz 50Hz, +/- 1Hz 50Hz, +/- 1Hz 60Hz, +/- 1Hz
Waveform
Quasi Squarewave
Quasi Squarewave
Quasi Squarewave Quasi Squarewave
Quasi Squarewave
Sl ew Rate
< 100 Volts/ms
< 100 Volts/ms < 100 Volts/ms
< 100 Volts/ms
< 100 Volts/ms
Crest Ratio (Peak: RMS) 1.3:1 1.3:1
1.3:1
1.3:1 1.3:1
Effici ency @ 87Vrms On-Li ne Rest Mode
@ 100 % Load 91% 91% 91%
91% 91%
@ 80 % Load 90% 91% 91%
90%
91%
@ 60 % Load
89%
89%
89%
88% 89%
@ 40 % Load
85%
85% 84%
85%
85%
Effici ency @ 87Vrms Inverter Mode 48VDC
@ 100 % Load
88%
86% 86% 87% 88%
@ 80 % Load
87%
87%
87%
87%
87%
@ 60 % Load
86%
86%
86%
87% 86%
@ 40 % Load
81%
81% 81% 83%
81%
Foldback
(Near Short Circui t Current)
87 Volt Tap
22A 19A
21A
N/A 32A
75 Volt Tap 20A 21A
24A
N/A 29A
60 Volt Tap
19A 27A
27A
21A
36A
(Max Knee Current (Start-Up Power)
87 Volt Tap % Rated Current 150% 150% 150% N/A 165%
75 Volt Tap % Rated Current
155%
180%
160%
N/ A
192%
60 Volt Tap % Rated Current 180%
210% 180% 150% 234%
>110% (3 hour Cyclic Operation)
30 Sec. On, 30 Sec Off >16.5A
>16.5A
>16.5A
>16.5A N/A
Severe Overload (3 hour Cycli c Operation)
6 Sec. On, 26 Sec. Off
>21A
>21A >21 A
>21 A 27.25A
Unit Weight 60 lbs (27kg) 59 lbs (27 kg)
66 lbs (30kg)
55 lbs (25 kg)
69.5 lbs (32 kg)
DC Battery Breaker
Envi ornmental
Operating Range
Humi di t y
Elevation
DC Electri cal
DC Input Voltage
Constant Current
Constant Voltage
DC Charge Current
Low Battery Cutoff
-40 degrees C to +55 degrees C at front air inlet of power suppl y
0 to 95% (non condensing)
0 to 10,000 feet (3000 meters) above sea level
48 VDC
High rate charge, threshold at 2.35 VPC
2.35 VPC (Maximum 48 hours)
6-12A Maximum, depending on load
<1.75 VPC
3: Batteries