3.0 Installation Instructions for Speci c Power Supplies
These are speci c installation instructions for standby power supplies supported by the XP-EDH-A
transponder. Each set of instructions include the interface card settings, a system diagram, and the
output voltage calibration needed to successfully operate.
NOTE:
All settings and instructions speci ed here supercede information found in previous manuals.
3.1 Alpha XM2 Series
ATTENTION:
Alpha XM and XM2 power supply installations using USM2 (both new and old versions) and USM2.5 cards
require switch/jumper settings to be made for proper operation.
If commercial power is present at the site and the power supply is currently being
powered by commercial AC line voltage, then turn the battery breaker OFF on the inverter
module.
1.
NOTE:
When monitoring commercial line power, the XM2 (with the USM2.5 card) does not require an input voltage
transformer because the USM2.5 card provides a scaled voltage representing the line input to the power
supply. In this situation, the transponder makes the measurement via the interface cable connected to the
USM2.5 card.
3.1.1 USM2.5 Jumper Settings
Fig. 3-1, USM2.5 Switch/Jumper Settings
Settings for <48V an >=20A
Settings for 48V an >=20A
Settings for 48V an <20A
Settings for <48V and <20A
Determine the characteristics of the power supply, such as the inverter voltage (36 or 48),
and the maximum capable output current (typically <20A or >20A).
Slide the inverter drawer out to gain access to the switches or jumpers located on the
various types of USM2 and USM2.5 cards. If you need to install a USMx card, refer to the
manual supplied with the card and complete the installation process.
Refer to the following diagram and adjust the switch settings to match your power supply.
Close the inverter module and tighten the retaining screws.
2.
3.
4.
5.
NOTE:
Turning the battery breaker OFF disables standby power.