CFR 7.
! Operator’s Manual ! CFR 7.
CFR 7.5K, 10K, 15K Save This Manual It contains important installation and operating instructions. Keep it in a safe place. CAUTION Risk Of Electrical Shock To reduce the risk of electrical shock and to ensure the safe operation of the CFR 7.5K, 10K, 15K, these symbols are used throughout this manual. Where they appear only qualified personnel should carry out the instructions. A DANGEROUS VOLTAGE exists in this area. Use extreme caution. ATTENTION: Important operating instructions.
CFR 7.5K, 10K, 15K Safety Checklists DANGER: Do not expose the unit to rain or moisture. DANGER: Sealed lead-acid batteries with high energy and chemical hazards are used. This manual contains important operation and safety instructions. Only qualified personnel should service the CFR 7.5K, 10K, 15K. CFR 7.5K, 10K, 15K UPS Safety Checklist Carefully unpack the unit. Report any shipping damage at once. Read this manual.
CFR 7.5K, 10K, 15K Safety Checklists (Continued) There are dangerous voltages inside the unit. Only qualified personnel should perform installation and maintenance. Live battery wires must not touch the unit’s chassis or any other metal objects. This can cause a fire or explosion. Inspect the batteries once a year for signs of cracks, leaks or swelling. Replace as required. When batteries are in storage, charge them at least once every three months for optimum performance and to extend their lifetime.
CFR 7.5K, 10K, 15K Table of Contents The emergency shutdown procedure is on the inside rear cover 1. Introduction ......................................... 1 1.1 The CFR Advantage .................................. 1.2 The Alpha CFR 7.5K, 10K and 15K .......... 4. Communication 2 3 Setting Up RS–232 Communications ..... 38 Using the Opening Menu ........................ 40 Menu Tree .............................................. 43 System, Input, Output & Battery Parameters ...........................
1 Section 1 Introduction This section introduces you to the Alpha 7.5K, 10K and 15K CFR UPS’s: • The CFR advantage (Section 1.1). • An tour of the unit, it’s connectors, switches and control panels (Section 1.2).
1 Introduction 1.1 ! 2 The CFR Advantage Advanced Power Protection Technology Alpha’s CFR Uninterruptible Power Supply (UPS) provides continuous and conditioned computer-grade AC power for computer systems, point of sale terminals, process controls, telecommunications, cable TV headend, broadband LAN, manufacturing control systems, hospital critical care and lab equipment. ! Regulation The unit maintains ±1% output regulation without using the batteries.
3 1.2 1 Introduction The Alpha CFR 7.5K, 10K and 15K Save The Original Shipping Container If you need to return the unit for servicing, pack it in the original shipping container. Alpha is not responsible for damage caused by the improper packaging of returned units. Read This Manual Before installation, become familiar with your unit by reviewing the procedures and drawings in this manual.
1 Introduction 1.2 4 The Alpha CFR 7.5K, 10K and 15K (Continued) 1.2.1 Front Panel Display Panel This is either the Standard Interface Display (SID) (Section 3.5) or the optional Intelligent Interface Device (IID) (Alpha manual #018–029– B0–001). Front and Side Panels These panels are removable to allow access to the unit’s interior in order to change the batteries, perform maintenance, etc. (Section 2.3).
5 1.2 1 Introduction The Alpha CFR 7.5K, 10K and 15K (Continued) 1.2.2 Rear Panel Figure 1.1 Rear Panel Fans These four fans cool the unit. They must not be blocked. Output Terminal Block This is the unit’s output power connector. See Section 2.6 for wiring information. The cover plate strain relief accepts either ¾ or 1 inch conduit. Output Circuit Breaker This provides protection to the load and can be used as an output power on/off switch.
1 Introduction 1.2 6 The Alpha CFR 7.5K, 10K and 15K (Continued) Input Circuit Breaker This provides protection for the unit. It can be used as an input power on/off switch. Input Terminal Block This is the unit’s output power connector. See Section 2.6 for connection information. The cover plate strain relief accepts either ¾ or 1 inch conduit. Battery Circuit Breaker This protects the unit’s inverter and DC circuits and can be used as a battery power on/off switch.
7 1.2 1 Introduction The Alpha CFR 7.5K, 10K and 15K (Continued) External Alarm Connector This RJ–45 connector allows the connection of an external alarm panel or an emergency shutdown switch (Section 2.8). RS-232 Connector This DB–9 port provides RS–232 communication (Section 2.9). External IID An external IID plugs into this connector for remote control and monitoring.
8 Section 2 Installation This section shows you how to unpack, install and connect the Alpha 7.5K, 10K and 15K CFR UPS’s: • A pre-installation checklist (Section 2.1). • How to unpack and transport the unit (Section 2.2). • How to connect the internal batteries (Section 2.3). • How to secure the unit with the seismic brackets or the wheel locks (Sections 2.4 and 2.5). • How to wire the unit’s input and output terminal blocks (Section 2.6).
9 2.1 2 Installation Pre–Installation Checklist 2.1.1 Site Preparation Install the unit upright in a dry, well-ventilated, dust free environment. There must be at least 6 inches (152 mm) between the unit and the wall(s) for cooling and access to the front and rear panels. Do not place the unit next to air conditioning or heating thermostats. Do not connect the unit to line conditioning equipment. This can cause improper operation of both the unit and the equipment.
2 Installation 10 2.1 Pre–Installation Checklist (Continued) The unit should be wired to dedicated circuit equipped with a properly sized circuit breaker. The breaker’s size is the unit’s maximum input current (as given in the specifications) plus 25%. For example if the unit draws 32.0 Amps of current at 208 VAC, adding 25% the input current becomes 40.0 Amps. A 40 Amp circuit breaker would be OK. Always follow the local electrical code when installing or sizing circuit breakers.
11 2.2 2 Installation Unpacking and Transportation TIP: If items are missing or damaged, contact Alpha and the shipping company at once. Most shippers have a short claim period. WARNINGS: 1) Before unpacking the unit, make sure that the shipping pallet is on a level working surface and that you can access the front of the pallet with a forklift. To prevent damage, move the unpacked unit as close as possible to the installation site.
2 Installation 2.2 12 Unpacking and Transportation (Continued) 2 Remove the corner support pieces by lifting them up and away. 3 Remove the screws holding these plywood strips to the pallet with a Phillips screwdriver. Lift the box off the pallet. 4 Remove the plastic wrap from around the unit.
13 2.2 2 Installation Unpacking and Transportation (Continued) 5 Attach vice grips to the bolt shaft or attach a / inch socket wrench to the bolt head from under the pallet to prevent the bolt from moving while you unscrew the nuts. 15 16 Using a 15/16 inch socket wrench, remove the four nuts securing the unit to the pallet 6 Pull the front lower panel forward to remove it.
2 Installation 2.2 14 Unpacking and Transportation (Continued) WARNING: Do not let the forks extend out past the back of the unit. 8 Lift the unit off of the pallet. Remove the wood / foam shock absorber. Transport it to the installation site.
15 2.3 2 Installation Connecting the Internal Batteries For safety reasons the 7.5K and 10K unit’s internal batteries have been disconnected at the factory. The 15K unit does not have internal batteries (See Section 2.7, “Connecting the External Battery Packs”). Before installation, the unit must be opened and the batteries connected. This procedure should only be done by qualified personnel. DANGER: Do not let any of the panels touch internal components.
16 2 Installation 2.3 Connecting the Internal Batteries (Continued) 4 Move the panel up about 1 inch and pull it forward. 3 Remove the two Phillips TIP: Both the SID and IID are attached to the front panel. Do not damage or disconnect the ribbon cables connecting them to the unit. screws located along the base of the unit’s front panel. 6 5 Remove the two Phillips screws on the unit’s rear panel. Remove the cover by carefully lifting it straight up.
17 2.3 2 Installation Connecting the Internal Batteries (Continued) Step 2: Connect the Batteries DANGER: There is up to 165 VDC inside the unit when the batteries are connected. Take great care when working inside it. Make sure the side panels do not touch any internal components. For more information on battery handling, see the safety instructions in the front of this manual. Procedure: 1 Make sure the input, output and battery circuit breakers are turned off. 2 Locate the battery connectors.
18 2 Installation 2.4 Mounting the Seismic Brackets TIP: The seismic brackets can be removed if they are not required by local code or you are not in an earthquake zone. Also see Section 2.5, “Locking the Wheels.” If the brackets are used to secure the unit to a concrete pad, go directly to 5. DANGER: Removing the side panels exposes dangerous voltages. Use extreme caution. Also see Section 2.3, “Connecting the Internal Batteries.” Tools and Materials Required: • Phillips screwdriver.
19 2.4 2 Installation Mounting the Seismic Brackets (Continued) 5 Mark the position on the floor where the unit will be secured by using the bracket as a template. Drill holes and secure using the appropriate anchor bolts. The drawing below looks down unto the bracket and the floor: 0.562 inch diameter for mounting 0.5 inch (13 mm) anchor bolts. 0.781 inch diameter for mounting 0.75 inch (19 mm) anchor bolts (such as Hilti #665927 (HSL M12/25)). Bracket Removal/Mounting Finished 2.
2 Installation 2.6 20 Connecting the Terminal Blocks WARNINGS: 1) Wiring should meet all local electrical codes and be done only by qualified personnel. 2) Before starting make sure the circuit breaker providing power to the unit is turned off. Tools and Materials Required: • Phillips screwdriver. • Wire as listed in Figure 2.1. • ¾ inch or 1 inch conduit. Procedure: 1 Turn off the rear panel’s: • Output circuit breaker. • Input circuit breaker. • Battery circuit breaker.
21 2.6 2 Installation Connecting the Terminal Blocks (Continued) 4 Replace the cover plate. 5 To wire the output terminal block, repeat 2 to 4 , except wire the output to the load(s). Wiring Finished CFR Mo d el 7.5K , 10K 15K In p u t /Ou t p u t Ter m in al B lo c k s AWG mm m m2 6 13.3 4 Tig h t en in g To r q u e In c h -Po u n d s N-m 35 35 4.0 21 21 Figure 2.1 Terminal Block Wire Sizes and Tightening Torques 2.
22 2 Installation 2.7 Connecting the External Battery Packs (Continued) Procedure: 1 Verify the battery circuit breaker is off. Keep it off until after the unit has been started with line power. 2 Verify the correct DC voltage and polarity at the battery pack’s connector It should be between 145 VDC to 165 VDC. TIP: Wrong voltages or polarities could damage the unit and the battery pack. 3 Loosen the cover plate and slide it up to expose the connector. 4 Plug in the connector.
23 2.7 2 Installation Connecting the External Battery Packs (Continued) Disconnecting the EBP The EBP connector has a lock to firmly attach it to the unit. To unlock it, use a slot-head screwdriver as shown below. Put screwdriver in connector lock. 1 EBP Connector (TopView) Unit Interior 2 Push screwdriver up to push lock down. Slide connector out once lock has cleared unit’s top edge. EBP Connector (Side View) Unit Interior Figure 2.
24 2 Installation 2.8 Connecting the External Alarm Port An external alarm panel can be connected to the external alarm port (Figure 2.4). The port’s contacts are rated at 30 VDC at 1 Amp. An Emergency Power Off (EPO) switch is created by wiring a switch to Pins 7 and 8. • Pushing the EPO switch automatically switches off the unit’s battery circuit breaker. • The contacts must be shorted for at least 1.5 seconds with unit shutdown about 2 seconds after the shorting starts. • The switch must be a SPST, N.
25 2.9 2 Installation Connecting the RS–232 Port The unit can be remotely setup, monitored, and tested by connecting the unit’s DB–9 connector to a computer’s serial port (Figure 2.5) or communication via a LAN with an optional SNMP agent. Windows HyperTerminal or any other terminal emulation program is used to communicate with the unit. Section 4 gives more information.
26 2 Installation 2.10 Transformer Output Load Sharing 2.10.1: Transformer Output The units have a single phase output. It does NOT have three phase characteristics. Figure 2.6 shows the voltages between L1, L2 and N for 120/208/240 units and between L and N for 230 VAC units 60 Hz Units FERRO TRANSFORMER 50 Hz Units 240 VAC FERRO TRANSFORMER 32 VAC L 208 VAC 120 VAC 120 or 88 VAC 88 VAC NEUTRAL L1 120 VAC 240 or 208 VAC 230 VAC 120 VAC N Figure 2.6 Transformer Output 2.10.
27 2.10 2 Installation Transformer Output Load Sharing (Continued) 2.10.2.1: Measuring the Output Current This uses a clip-on current probe (Figure 2.8 for 240 VAC, Figure 2.9 for 208 VAC and Figure 2.10 for 230 VAC). For 120/208/240 VAC units the total current drawn from Winding 1 is the sum of the currents A, B and C where: • A is the total current drawn by all of the 120V loads connected to the receptacle. • B is the total current drawn by all of the 240V loads connected to the receptacle.
28 2 Installation 2.10 Transformer Output Load Sharing (Continued) The total output current for 230 VAC units is measured at A. A L 230 VAC Receptacle 230 VAC N Output Terminal Block Figure 2.10 230 VAC Current Measurement Point 2.10.2.2: Displaying the Output Current TIP: When using the display panels, you must calculate L1’s current as described below. Using the SID Display Panel: The current is displayed via RS–232 as Output Current 1 and Output Current 2 (Section 4.4.3).
29 Section 3 Operation This section shows you how to operate the Alpha 7.5K, 10K and 15K CFR UPS’s: • How to turn the unit on and off (Sections 3.1, 3.2). • How to start the unit’s self test (Section 3.3). • How to troubleshoot the unit with the SID (Section 3.4). • How to use the Standard Interface Device (SID) (Section 3.5).
3 Operation 3.1 30 Turning On the Unit WARNINGS: 1) This unit runs warm to the touch. During the first few weeks of operation, a brand new unit may give off an odor caused by the burning of the transformer’s lacquer finishing. This is normal and is not toxic. 2) The unit generates electromagnetic radiation. Keep all sensitive magnetic media such as floppy disks, recording tape, key cards, bank and credit cards away from it. Procedure: 1 Switch off: • All loads connected to the unit.
31 3.1 3 Operation Turning On the Unit (Continued) Cold Start Procedure This starts the unit with battery power when line power is unavailable or unqualified. Backup battery power is provided to the loads. 1 Switch on the Battery circuit breaker. 2 For units with the: • SID display panel, press the Manual Start button. The unit’s alarm beeps every 20 seconds, indicating it is running on battery power. • IID display panel, press the Test button. Cold Start Finished 3.
3 Operation 32 3.3 Testing the Unit The self test confirms the unit can switch from line power to backup battery power and back without interrupting power to the loads. It takes about one minute to run. Before starting: • For 15K units, the external battery pack must be connected. • The Battery circuit breaker must be on. • The control panel’s Line Present LED must be on. Procedure: 1 Press the Manual Start button down for 5 seconds.
33 3 Operation 3.4 Troubleshooting With the SID The SID’s Output Load LEDs have two functions: • When the unit is operating normally, it serves to show the unit’s output loading. • When the Service LED is on, the load LEDs are turned into a fault indicator for as long as the Alarm Off button is pushed and held down. TIP: See Section 5.2 for more troubleshooting information. Procedure: 1 When the Service LED is on, press and hold ALARM OFF down the Alarm Off button.
3 34 Operation 3.5 Controlling the Unit With the Standard Interface Device (SID) The Standard Interface Device (SID) display panel (Figure 3.2) shows vital operating parameters and starts the self test. It has two push buttons, five LEDs showing the power drawn by the loads and six LEDs showing the unit’s operating status. ALARM OFF MANUAL START LINE PRESENT LOW BATTERY WARNING LINE FAILURE LOW BATTERY SHUTDOWN SERVICE TEST OUTPUT LOAD OVERLOAD 100% 75% 50% 25% Figure 3.
35 3 Operation 3.5 Controlling the Unit With the Standard Interface Device (SID) (Continued) Low Battery Shutdown This red LED turns on when the battery voltage is 12% below nominal. The unit automatically shuts itself down and no longer provides power to the loads to prevent overdischarge damage to the batteries. Test This yellow LED shows the unit is in self test mode (Section 3.3). If it fails the test, the Service LED is on and the unit defaults to Line Present operation.
3 Operation 36 3.5 Controlling the Unit With the Standard Interface Device (SID) (Continued) Output Load These five green LED's show the unit’s loading as a percentage of its maximum output. The Overload LED is on if: • The output exceeds the unit’s maximum rating. • The output exceeds either of the transformer output winding ratings (Section 2.10). WARNING: Do not run the unit when it is overloaded. Damage to the unit, the inverter or the batteries can result.
37 Section 4 Communication This section shows you how to control the Alpha 7.5K, 10K and 15K CFR UPS’s with RS–232 computer commands: • How to set-up communications with Windows© HyperTerminal (Section 4.1). • How to understand and use the opening menu (Section 4.2). • A description of the menu tree (Section 4.3). • Descriptions of the system, input and output and battery parameters menus (Section 4.4). • Descriptions of the user and maintenance parameters (Sections 4.5 and 4.6).
4 Communication 38 4.1 Setting Up RS–232 Communications Wire the DB–9 connector as shown in Section 2.9, “Connecting the RS–232 Port.” Windows HyperTerminal Connection For this tutorial, Com 1 is used and the unit is called CFR. Procedure 1 The path is Start/Programs/Accessories/ Communications/HyperTerminal. 2 Click on the Hypertrm.exe icon. The Connection Description screen appears (Figure 4.1). Enter a name and choose an icon for your unit. Click OK. Figure 4.
39 4 Communication 4.1 Setting Up RS–232 Communications (Continued) 4 The Com 1 Properties screen appears (Figure 4.3). Fill out the fields as shown. 5 Click OK. Figure 4.3 COM 1 Properties Screen 6 The CFR Screen appears. 7 Press Enter to go to the Opening Menu (Figure 4.4). The Opening Menu (Figure 4.5) appears.
4 Communication 4.2 40 Using the Opening Menu The opening menu (Figure 4.5, also see Figure 4.4) is the top-level menu. It shows the line’s status, displays if any alarms are present and gives access to the main menus. It is reached from anywhere in the menu tree by pressing Enter. The entire menu tree is given in Section 4.3. Tables describing the main and sub menus are given in Sections 4.4 to 4.7. Procedure: To access a particular main or sub menu, type in the number and press Enter.
41 4.2 4 Communication Using the Opening Menu (Continued) Figures 4.6 to 4.9 list the alarms, how they appear on the screen and what they mean. In p u t Alar m s N am e S h o w s o n S c r een F r eq u en c y L o w FREQ_L O The input frequency is low. F r eq u en c y H i FREQ_HI The input frequency is high. Glit c h GL ITCH The unit detects a glitch. Sp i k e SPIK E The unit detects a spike.
4 42 Communication 4.2 Using the Opening Menu (Continued) Ou t p u t Alar m s N am e S h o w s o n S c r een Ou t p u t Vo lt ag e Low VOLT_L O C au s e The unit is over loaded or there is a unit fault. Reduce the number of loads connected to the unit. This can be caused by: Ou t p u t Vo lt ag e Hig h --A piece of equipment that draws power at irregular intervals. Disconnect the suspect equipment and see if the alarm repeats. VOLT_HI --The unit is defective. Have it serviced by Alpha.
43 4 Communication 4.3 Menu Tree • To reach any main or sub menu from the opening menu, type its number and press Enter. • Detailed descriptions of each menu is given in Sections 4.4 to 4.7.
4 44 Communication 4.4 System, Input, Output & Battery Parameters Main menus #1 to #4 are read only menus which display important operating parameters. 4.4.1 Main Menu #1: System Parameters This displays the battery temperature (°C) and starts and stops the self test. • Sub menu 11 starts the self test. The test’s default duration is 60 seconds. • Sub menu 12 lets you stop the test before it has finished. 4.4.2 Main Menu #2: Input Parameters This displays selected input parameters.
45 4 Communication 4.4 System, Input, Output & Battery Parameters (Continued) 4.4.3 Main Menu #3: Output Parameters This displays selected output parameters. See Figure 4.12 for 120/208/240 VAC, 60 Hz units to see where the voltages and currents are measured. See Figure 4.13 for 230 VAC, 50 Hz units. TIP: If the unit has dual outputs, you have the option of displaying the voltage and current of each output individually.
4 46 Communication 4.4 System, Input, Output & Battery Parameters (Continued) L 230 VAC Receptacle Output Voltage 1 N Output Current 1 Output Terminal Block Figure 4.13 Output Voltage and Current Measurement Points (230 VAC, 50 Hz Units) 4.4.4 Main Menu #4: Battery Parameters This displays the battery voltage, the charger current and the charger’s status. Item #40 is disabled in this model. B at t er y P ar am et er s This is the DC voltage of the battery string.
47 4 Communication 4.5 User Parameters Main menu #5, user parameters, lets you set up the automatic self test, remotely shut down the unit, change the password and set up RS–232 communications with or without an external modem. To access most of these functions, you need to enter a password. The factory set password is 1111. If you change it (Items #58 and #59), make sure you keep a copy of it in a safe and easily accessible place or you will not be able to access the unit. 4.5.
4 Communication 48 4.5 User Parameters (Continued) Us er Par am et er s (Co n t in u ed ) 56 56 Tr an s m it U n s o l i c i t ed A l ar m s This allows you to start or stop the transmission of unsolicited alarms. This menu's use is explained in Section 4.5.3, "Sub Menu #56: Transmit Unsolicited Alarms." This lets you change the password. 58 58 S et U s er S ec u r i t y C o d e The factory set password is 1111. If you change it, make sure you keep the new code in a safe, secure place.
49 4 Communication 4.5 User Parameters (Continued) Set Ou t p u t Sh u t d o w n Par am et er s (Co n t in u ed ) This starts the shutdown. The 6 Power LEDs on the display panel flash in sequence to show the unit is alive, but the output is turned off.
4 50 Communication 4.5 User Parameters (Continued) 4.5.3 Sub Menu #56: Transmit Unsolicited Alarms These menus allow you to prevent or delay the continuous transmission of alarms in areas with unstable line power. Tr an s m it Un s o lic it ed Alar m s 509 D i s ab l e Tr an s m is s io n o f U n s o l i c i t ed A l ar m s Setting this to "Active" stops the transmission of all unsolicited alarm messages. "509 None (xxxx)" where xxxx= "Active" or blank. Active is default.
51 4 Communication 4.6 Maintenance Parameters Main menu #7, maintenance parameters, allows you to adjust the unit’s detection and warning parameters to suit your local line conditions. Usually these factory settings never have to be changed. CAUTION: Improper settings can damage the unit. If you have any questions, contact Alpha Technologies before changing them.
4 Communication 52 4.7 Installing and Using the External Modem Uses of the External Modem Where a network is not available, you can connect an external modem to the CFR’s RS–232 port. The modem lets you: • Program the CFR to send an alarm message to a remote host via the telephone line when a power event takes place. • Dial up the CFR for remote monitoring or control. Once connected, all RS–232 menus are accessible.
53 4 Communication 4.7 Installing and Using the External Modem (Continued) Step 1: Enable the CFR’s Modem Feature The CFR is shipped with the modem feature disabled. To enable it: 1 Connect a computer to the CFR’s RS–232 port (Sections 2.9, 4.1). 2 Go to Menu Item #52 (Figure 4.19). (For explanations of each item see “Modem Setup and Control: Sub Menu #52” in this section.
4 54 Communication 4.7 Installing and Using the External Modem (Continued) Step 2: Connect and Configure the Modem Use a shielded, null-modem serial cable, DB–25 male to DB–9 male, to connect the modem to the CFR. 1 The most common ways to connect the cable are: • A null-modem cable with DB–25 male to DB–-9 male ends (Figure 4.20). • A null-modem cable with DB–25 male to DB–25 male ends and a 9–25 adapter. • A standard straight-through cable with DB–9 male to DB–25 female and a nullmodem adapter.
55 4 Communication 4.7 Installing and Using the External Modem (Continued) 3 The initialization string (Item #527) is a set of commands the CFR sends to the modem to initialize it. For a US Robotics modem, the string is: • ATX4Q0V1&H0&R1&I0&B1 Where: • X4: Extended set of result codes. • Q0: Result codes are displayed. • V1: Display verbal (words not numbers) result codes. • &H0: Disable transmit data flow control (neither hardware “CTS” nor software “Xon/Xoff” flow control).
4 Communication 56 4.7 Installing and Using the External Modem (Continued) Step 3: Initalize the Modem To initalize the modem start a CFR self test (Section 3.3). The CFR must initialize the modem. If a remote host calls before initialization, the CFR/ modem combination will not answer the call. TIP: If the modem is set for auto answer and a call is answered before the CFR initalizes it, the modem uses its own baud rate which may not be the 1200 baud used by the CFR.
57 4 Communication 4.7 Installing and Using the External Modem (Continued) How the CFR Sends Alarms To send an alarm, the CFR sends the dial command to the modem and waits up to 60 seconds for a “connect.” If this fails, it will try the same dial command two minutes later if the modem responds back to the CFR with a “No Carrier,” “No Dial Tone” or “Busy” messages. If the modem does not respond (it is disconnected, not powered or is inoperable), the CFR tries to initalize the modem.
4 58 Communication 4.7 Installing and Using the External Modem (Continued) Ex t er n al Mo d em Set u p Men u s 520 E n ab l e A u t o m at i c A l ar m s Enable this feature near the end of the configuration session since the CFR will try to communicate with the modem two minutes after this feature is activated. When set to "Yes," this causes the modem to dial out and report a problem when it occurs (see Item #522). The default value is No.
59 4 Communication 4.7 Installing and Using the External Modem (Continued) Ex t er n al Mo d em Men u Set u p Men u s (Co n t in u ed ) 523 Set In v er t er A l ar m D el ay Setting this delays the transmission of "UPS003-Inverter on" messages for 1 to 5 minutes to prevent short interruptions in the line from being displayed. Setting it to 0 causes the immediate sending of the message.
60 Section 5 Maintenance This section describes how to maintain the Alpha 7.5K, 10K and 15K CFR UPS’s: • How to measure the battery backup time (Section 5.1). • How to troubleshoot the unit (Section 5.2). • How to return the unit to Alpha for repair (Section 5.3). • How to replace the 7.5K and 10K unit’s internal batteries (Section 5.4). • How to change the unit’s input and output voltages (Section 5.5). • Typical battery run times (Section 5.6). • Specifications (Section 5.7).
61 5 Maintenance 5.1 Testing the Battery Backup Time This test measures how long the batteries can provide backup power by having them power the loads until they are discharged. Tips: • This test should be done once a year when the batteries are new. When the batteries are three years old or older, it should be done once every six months. • This test should be done when new loads are connected to the unit.
5 62 Maintenance 5.2 Troubleshooting Most problems involve: • Are the Input, Battery and Output circuit breakers switched on? • Is the input voltage correct? • Are the batteries expired? If the unit fails to perform a specific function, Figure 5.1 lists typical symptoms, causes and solutions, starting with the most obvious and working systematically. If you cannot resolve a problem, contact Alpha’s customer service department. The unit’s electronics require no maintenance.
5 63 5.2 Maintenance Troubleshooting (Continued) Sy m p t o m C au s e No output. The Line Present and Line Failure LEDs are off or the Line Present is flashing. Line power absent or out of tolerance and the batteries are not connected. R em ed y Check the input voltage. Check the battery connections. Input circuit breaker off. and Battery circuit breaker off. Check to see both breakers are on. No output. Line Present LED or Line Failure LED is on. The output circuit breaker is off. Turn it on.
5 64 Maintenance 5.3 Returning the CFR to Alpha for Repairs If you need to return a unit for repair, obtain a Return Material Authorization (RMA) number from Alpha Technologies’ customer service department. Clearly write it on the original shipping container. If you do not have the container, pack the replacement with at least three inches of shock-absorbing material, but do not use popcorn type packaging. Returns should be prepaid and insured (COD and freight collect cannot be accepted).
5 65 5.4 Maintenance Replacing the Internal Batteries (Continued) Step 1: Remove the Front Panel and Left Side Cover Remove the front, left side and top panels as described in Section 2.3, “Connecting the Internal Batteries,” Step 1, “Open the Unit.” Step 2: Charger Voltage Test This tests the unit’s battery charger so the new batteries will not be damaged by a faulty charger. Do this before disconnecting the batteries. Procedure: 1 Make sure: • The battery circuit breaker is switched off.
5 Maintenance 5.4 Replacing the Internal Batteries (Continued) Step 3: Replace the Batteries Procedure: 1 Switch off the battery, input and output circuit breakers. 2 Disconnect the battery connectors. (TIP: The wires are numbered for easy reconnection [1 into 1, 2 into 2, etc.]). 3 Unscrew (1/4 inch hex screws) and then remove the front plate holding the battery trays in place. 4 Slide the three battery trays out. 5 Remove the battery wires. 6 66 Remove the battery retention bar.
5 67 5.4 Maintenance Replacing the Internal Batteries (Continued) 7 Replace the batteries. 8 Replace the battery retention bar. 9 One tray at a time, wire the batteries together as shown in Figure 5.3. Do not wire the battery trays to each other. Red connectors Unit Rear Unit Front Black connectors Figure 5.3 Internal Battery Connection 10 Repeat steps 4 to 2 in reverse order to replace the batteries. 11 Replace the covers (Step 1). 12 Re-start the unit (Section 3.1).
5 Maintenance 5.5 68 Configuring the Input/Output Voltage The input and output voltages are factory configured to your specifications. You can change them with this procedure. DANGER: Lethal levels of voltages and currents are inside the unit when it is connected to line and battery power. All circuit breakers on the rear panel must be turned off before starting this procedure. Procedure: 1 Confirm all the rear panel circuit breakers are switched off.
5 69 5.
5 70 Maintenance The times in these charts are to be used in conjunction with the battery run time you measured in Section 5.1, “Testing the Battery Backup Time.” Tips: • Your run time can vary by ± 15%. Battery run time is affected by temperature, battery age and condition and the size and type of the loads. • End of battery life is defined when the battery capacity falls below 80% of rated capacity. • Times shown are averaged over a batch. • All battery voltages are 144VDC.
5 71 5.
5 72 Maintenance 5.7 Specifications In p u t , Ou t p u t C i r c u i t P r o t ec t i o n In p u t Fr eq u en c y (Hz ) 50 ± 3 60 ± 3 Ou t p u t Fr eq u en c y (Hz ) In v er t er m o d e 50 ± 0.1 60 ± 0.1 Ou t p u t Reg u lat io n (VAC) ± 1% In p u t Vo lt ag e Var iat io n -20% to +10% VAC To t al Har m o n ic Dis t o r t io n <5% (non-linear loads; <2.
5 73 5.7 Maintenance Specifications (Continued) CFR UPS SPECIFICATIONS 7.5K 7.5E 10K 10K E 15K 15K E Ou t p u t Po w er (VA) 7500 10000 15000 Ac t iv e Po w er (W) 5000 6700 10000 In p u t Vo lt ag e @ 50 Hz (VAC) --------- 230 --------- 230 --------- 230 In p u t Vo lt ag e @ 60 Hz (VAC) 208/240 --------- 208/240 --------- 208/240 --------- In p u t Cu r r en t @ 208(240) VAC (Am p s ) 1 32.0 (27.5) --------- 40.0 (35.0) --------- 58.0 (51.
Index A Adjusting Unit to Local Line Conditions ............... 51 Alpha, Returning Unit to for Repair ...................... 64 Alarm Off Button on SID Panel .............................. 35 Alarms On Display Panel ........................................... 34–36 RS–232 ......................................................... 40–42 Starting/Stopping of RS–232 Transmission ......... 50 Alarms, Turning Off Audible Alarm ....................... 35 Alarm Port, use of and Wiring .............................
75 Index Pre–Installation ............................................... 9–10 Emergency Power Off Switch ................................ 24 Common Problems ............................................ 62–63 Emergency Shutdown Procedure ............................. ....................................................... Inside Rear Cover Computer Also See RS–232 Communications Communications Parameters ........................ 25, 39 Connecting to a Computer ..................................
Index 76 Inspection Checklist ......... See Unpacking Checklist Installation Installation Checklist ....................................... ii, 11 Installation Sequence ......................................... 10 Inverter On/Off via RS–232 ..................................... 49 Internal Battery Replacement .......................... 64–67 Input, Output and Battery Parameters via RS–232 .. ................................ See RS–232 Communications Menu Tree, RS–232 .....................................
77 R Rear Panel ............................................................ 5–7 Reconfiguring Input/Output Voltage ................ 68–69 Remote Monitoring With Also See RS–232 Communications External Alarm Panel .......................................... 24 RS–232 .........................................................37–59 Remote IID ........................................................... 7 Index Shutdown Procedure Emergency .................................
Index U Unit Shutdown via External Power Off Switch .... 24 Unpacking Checklist ............................................... 11 Utility Line Acceptable Input Voltages ................................... 9 Adjusting Unit to Local Line Conditions ............... 51 Dedicated Circuit Breaker ................................... 10 Labels, on Utility Panel, Placing ........................... 9 Measuring via RS–232 ............................................ ................................
Warranty 79 LIMITED 24-MONTH WARRANTY AC PRODUCTS Alpha Technologies warrants its equipment to be free of manufacturing defects in material and workmanship for a period of 24 months from the date of manufacture. The liability of Alpha Technologies under this warranty is solely limited to repairing, replacing, or issuing credit for such equipment (at the discretion of Alpha Technologies), provided that: 1.
Emergency Shutdown Procedure The unit has more than one live circuit. During an emergency, line power may be disconnected at the unit’s input but power can still be present at the output. COMPLETE SYSTEM EMERGENCY SHUTDOWN PROCEDURE: Turn OFF the: 1 Output Circuit Breaker 2 Input Circuit Breaker 3 Battery Circuit Breaker ALTERNATE PROCEDURE: 1 Press down the Emergency Power Off (EPO) Switch for 3-5 seconds. Emergency Power Off Switch (mounted on wall) 2 Turn off the Input Circuit Breaker.
Alpha Technologies World HQ 3767 Alpha Way Bellingham, WA, USA 98226 Tel: (360) 647–2360 Fax: (360) 671–4936 Alpha Technologies 4084 McConnell Court Burnaby, BC, Canada V5A 3N7 Tel: (604) 430–1476 Fax: (604) 430–8908 Alpha Technologies Cartel Business Estate Edinburgh Way Harlow, Essex CM20 2TT, UK Tel: +44–1279–422110 Fax: +44–1279–423355 Alpha Technologies GmbH Hansastrasse 8 D-91126 Schwabach, Germany Tel: +49–9122–79889–0 Fax: +49–9122–79889–21 MTI Technologies P.O.