Operating instructions

7.3 Power Module Shutdown
When a power module needs to be removed from service, an Alpha APP60-S Service Power
Supply is recommended as an alternate non-standby power source to prevent interruption
to the cable plant. NOTE: When powering down a module, always switch the battery breaker
OFF before removing AC, otherwise the module will transfer into inverter operation.
Procedure
1. Plug the APP60-S "Jones" connector into the SPI (Service Power Inserter).
2. Plug the APP60-S power cord into the enclosure's convenience outlet. Switch the
APP60-S ON. NOTE: Verify that the 30 / 60 VAC selector is in the desired position.
3. Toggle the switch on the SPI from "ON" to "ALT".
4. Switch the battery breaker on the front panel of the AM Series module OFF, or remove
the fuse.
5. Unplug the AM Series module's power cord from the enclosure's convenience outlet.
6. Wait approximately 1 minute for the module's capacitors to fully discharge.
7. Disconnect the wires from the module's 10-pin terminal strip. Do not let the exposed
battery cables come in contact with the chassis or enclosure.
8. Remove the hold-down screw and carefully slide the module out of the enclosure.
CAUTION: The ferroresonant transformer generates heat and may cause burns if
handled with bare hands.
9. Reverse this procedure, when re-installing a module. Always test the power module
before toggling the switch on the SPI back from "ALT" to "ON".
APP60-S Service Power Supply
AC Line cord to enclosure's
convenience outlet
"Jones" connector to enclosure's
SPI (Service Power Inserter)
ON/OFF Switch
30 VAC / 60 VAC
Selector Switch
AC Output Fuse
AC Input Fuse
32