Technical data
9
ALPHA700
12.0 system schematic
using reverse/return
It is important to ensure that for all Alpha single and multi-boiler installations, the system should be
designed to provide an even flow of water through each boiler when the burner is firing, and that this flow
rate is not less than the minimum flow rate shown for each size of boiler in the technical data.
On multi-boiler installations, even flow can be achieved by connecting the boilers to the water flow and
return pipework using a reverse return method of connection.
This will provide an even water flow through each boiler and ensure that the pressure loss across any
number of boilers is never greater than that for a single boiler plus adjacent pipework losses.
Constant Temp. Circuit
Primary
Circulating
Pump
3-Way Vent Valve
Gate
Valve
Boiler
No.1
No.2
No.3
Water
Sensor
Zone
Controls
Thermometer
Open Vent
Safety Valve
Boiler Sequence Controller
Zone 2
Zone 1
Mixing Valve
It is desirable to prohibit flow of water through a non firing boiler in a multiple boiler bank. One such
way is to install divertor valves and boiler bypass as shown below.
If this option is to be followed, then overrun timers must be incorporated into the control scheme to
allow any latent heat contained within the boilers to be scrubbed off before by-passing a boiler via the
operation of the divertor valve.
13.0 system schematic
using diverter valves
Constant Temp. Circuit
Primary Circulating Pump
3-Way Vent Valve
Diverter Valve
Boiler
No.1
No.2
No.3
Water
Sensor
Zone
Controls
Thermometer
Open Vent
Safety Valve
Boiler Sequence
Controller
Zone 2
Zone 1
Mixing Valve
Isolating Valves
Gate Valve
Balancing
Valve










