Technical data
19
ALPHA700
20.0 mounting
the burner
The supplied burner must be securely mounted to the front of the boiler via the mounting plate provided
and following the instructions supplied with the burner. The maximum length of the burner blast tube must not
exceed 220mm.
If it is necessary to pare away the ceramic fibre insulation of the burner door to allow burner blast tube
entry, then this should be done carefully using a hacksaw blade or similar and ensuring that the blast tube is a
snug fit through the hole in the door insulation. If the hole is oversized then the gap around the blast tube
should be packed with ceramic fibre wool from the combustion chamber side of the door.
If required, a cooling air line may be connected between the burner air test point and the connection on
the combustion chamber viewing window carrier using silicon rubber or similar tubing. This will provide a
cooling to the sight glass and assist in keeping it clean.
21.0 controls
Each boiler is supplied with boiler high fire and low fire control thermostats, manual reset on/off switch
and high limit test switch.
Whilst the following devices are not supplied, the boiler is designed to be compatible for use with the
following ancillary controls:
1. Time Clock/ Programmer 4. Sequence Control Panel
2. Room Thermostat 5. Compensating Equipment
3. Frost Protection Thermostat 6. Optimum Start/Stop Equipment
22.0 commissioning
procedures
22.1 electrical installation
Ensure that the electrical supply installation and burner electrical connection has been checked for earth
continuity and adequate fuse protection by a qualified engineer.
22.2 gas/oil installation (fuel installation)
Ensure that the whole of the fuel installation is inspected and tested for soundness and purged in
accordance with the relevant BS.
22.3 water circulation system
The whole of the system should be thoroughly flushed out with cold water, without the pump in position.
Ensure that all valves are open.
With the pump fitted, the system should be filled.
Vent all heat emitters, high pipework, clear airlocks, and check for water soundness.
22.4 flues
Make a general check of the flue system ensuring that draught is negative and stable, the flue is clear and
all joints are correctly sealed. Ensure also that the flue terminal is correctly positioned.
22.5 boiler
Check that boiler components are in position and correctly fitted, check boiler internal wiring is
undamaged, all connections including burner are properly made.
Light the boiler following as necessary specific instructions supplied with the burner.










