Specifications

2-2 Hardware Installation AlphaServer 1000A Owner's Guide
Selecting a System Location
When choosing a system location, keep in mind the optimal environmental conditions
and power requirements for the system. Be sure to keep the system in an upright
position. Figure 2-1 shows the system dimensions and the clearance needed to access
the system for servicing.
Figure 2-1 System Dimensions and Service Area
MA00908
35 cm
(14.1 in)
53 cm
(21 in)
44 cm
(17.4 in)
65 cm
(26 in)
1 m
(36 in)
Environmental Conditions
Table 2-1 lists the environmental conditions in which the system unit best operates.
Table 2-1 Optimal Environmental Conditions
Condition Specification
Temperature range
Relative humidity
Air circulation
Room temperature: Between 10º C and 40º C
(50º F and 104º F).
Between 10% and 90% (20% to 80% with
removable media options).
Allow a minimum clearance of 8 cm (3 inches)
on all sides of the system unit to allow sufficient
air circulation. Fans inside the system unit
circulate the air to prevent excessive heat, which
can damage the system components.