Alpha FXM350/ Micro350 UPS Installation and Operation Manual Part # 017-241-B0 Effective 11/11 member of The Group™ Your Power Solutions Partner
Alpha FXM350 and Micro350 UPS Installation and Operation Manual NOTE: Photographs contained in this manual are for illustrative purposes only. These photographs may not match your installation. NOTE: Operator is cautioned to review the drawings and illustrations contained in this manual before proceeding. If there are questions regarding the safe operation of this powering system, contact Alpha Technologies or your nearest Alpha representative.
Table of Contents 1. Safety ������������������������������������������������������������������������������������������������������������������������������������7 1.1 Safety Symbols �������������������������������������������������������������������������������������������������������������������� 7 1.2 General Warnings ���������������������������������������������������������������������������������������������������������������� 8 1.
7. Operating the FXM350 �������������������������������������������������������������������������������������������������������40 7.1 Switching the Alpha FXM On and Off ��������������������������������������������������������������������������������� 40 7.2 Operating from the Control Panel Interface ����������������������������������������������������������������������� 42 7.3 Operating via the FXM Communication Module (Intranet or Internet) ������������������������������� 49 7.
Figure 15 — Attaching the mounting bracket to the wall studs ������������������������������������������������� 27 Figure 16 — AC Power distribution terminal blocks ������������������������������������������������������������������ 28 Figure 18 — Terminal block wiring �������������������������������������������������������������������������������������������� 29 Figure 17 — Wiring the Micro350 ��������������������������������������������������������������������������������������������� 29 Figure 19 — Ferrite
���������������������������������������������������������������������������������������������������������������������������������������� 61 Figure 46 — Setting the Temperature trigger value ������������������������������������������������������������������ 61 Figure 47 — UPS Maintenance: Time & Date screen ��������������������������������������������������������������� 62 Figure 48 — UPS Maintenance: Password screen ������������������������������������������������������������������� 62 Figure 49 — User Inp
List of Tables Table A — UPS Operating Modes ��������������������������������������������������������������������������������������������������������� 43 Table B — Control Menu ����������������������������������������������������������������������������������������������������������������������� 45 Table C — System Status Menu ����������������������������������������������������������������������������������������������������������� 47 Table D — List of Parameters �������������������������������������������
1. Safety SAVE THESE INSTRUCTIONS: This manual contains important safety instructions that must be followed during the installation, servicing, and maintenance of the product. Keep it in a safe place. Review the drawings and illustrations contained in this manual before proceeding. If there are any questions regarding the safe installation or operation of this product, contact Alpha Technologies or the nearest Alpha representative. Save this document for future reference. 1.
1.2 General Warnings You must read and understand the following warnings before installing the product. Failure to do so could result in personal injury or death. • Read and follow all instructions included in this manual. • Only qualified personnel are allowed to install, operate and service this system and its components. CAUTION! Risk of Electric Shock. See Installation Instruction before connecting to the supply.
CAUTION! Never open, damage or mutilate batteries. Released Electrolyte is harmful to the skin and eyes. It may be toxic and hazardous to the environment. • Never dispose of batteries in a fire. The batteries may explode. Follow the manufacturer’s directions and check with your local jurisdictions for safe battery disposal. • If electrolyte splashes on your skin, immediately wash the affected area with water.
1.5 Certifications and Compliances The Alpha FXM350 and Micro350, has been designed, manufactured, and tested to the requirements of the following national and international safety standards: 10 • CAN/CSA-C22.2 No. 107.3-05 – Uninterruptible Power Systems; additional requirements (RD): CAN/ CSA-C22.2 No. 60950-1-03 - Information Technology Equipment - Safety.
2. General Description 2.1 Alpha FXM350 The Alpha FXM350 is available in 24Vdc and 48Vdc models. It provides up to 350W of regulated AC Power to the load, when utility power is available, and provides back up power from the batteries in case of a utility power failure.
In addition to the FXM350 standard features, the unit also includes the following: • Three additional user-configurable dry contacts and two additional user inputs (top panel in Figure 2) • Door sensor switch for increased security • AC Input and outputs on an easy to install terminal block • Flexible dual AC and DC output for multiple loads up to 350W with distribution AC input Battery bus voltage AC output (dual) 120Vac 48V or 24V 120/24Vac 230Vac 24V 230/24Vac Micro350 top panel FXM350 f
2.3 FXM350 Front Panel The following table and Figure 3 identify the main features of the FXM350 which are described in detail in the following pages.
6 Battery temperature sensor connector The battery charging voltage is temperature dependant. A battery temperature sensor connects to the Alpha FXM so that the Alpha FXM microprocessor can adjust the charging voltage for optimum charging. The sensor MUST be attached to the Alpha FXM for normal operation. If the sensor is not attached, a “Temperature Probe Unplugged” alarm appears on the LCD. 7 Battery voltage test points These test points let you measure the battery voltage.
11 Configurable dry contacts, C1 and C2 Contacts C1 and C2 allow the Alpha FXM to be connected to an external monitoring panel or to traffic control equipment. The factory default settings can be reprogrammed to meet your requirements. See "7.3.3.3 Monitoring > Relay & Load Shed" on page 53 for web and Alpha UPS Monitor, and "7.5.4 Programming the Dry Contacts" on page 82 for HyperTerminal.
2.4 Micro350 Top Panel The Micro350 top panel has three additional dry contacts and two user inputs. The panel also has a door interlock and auxiliary contacts, which can be wired to a user input to generate an alarm when the door is open. Dry contacts C3, C4, and C5 User inputs S3 and S4 Door interlock Open door switch signal Additional signals connector.
3. Site Planning WARNING! Restricted Access: The Alpha FXM350 and Micro350 must be installed in a restricted area accessible only by qualified service personnel. The Alpha FXM350 and Micro350 are intended for permanent AC connection only. The Alpha FXM350 and Micro350 must be correctly grounded for proper operation. Older facilities may have inadequate electrical grounding. Inspection must be performed by a qualified electrician before installation to ensure that grounding meets the local electrical code.
3.2 Electromagnetic Compatibility (EMC) Requirements Observe the following EMC requirements when setting up the Alpha FXM and its internal equipment: • All AC mains and external supply conductors must be enclosed in a metal conduit or raceway when specified by local, national, and/or other applicable government codes and regulations. • The customer facilities must provide suitable surge protection. • To meet FCC Class B requirements, follow the instructions in section 5.1.
Figure 8 — Mounting on optional pedestal 3.3.1 Battery Heater Mats The FXM350 and Micro350 allow connection, on its front panel, of a battery heater mat without a thermostat (#14 in Figure 3). Maximum power of the battery heater mat for use with the FXM350 connector is 55W. The FXM turns the heater mat on when the temperature measured by the battery temperature sensor senses a temperature < 5°C. It turns the heater mat off when the temperature raises to >15°C.
3.3.2 Mounting options for the FXM350 Figure 9 and Figure 11 provide dimensions for mounting the FXM350 UPS as a standalone device. 198 [7.8] 13.7 [0.5] 88 [3.5] 342 [13.5] Figure 9 — FXM350 Mounting Dimensions 3.3.2.1 Standalone Configurations: • Wall mounted, with front access, onto a 19" mounting tray that includes a battery cabinet • Rack mounted in a 19" or 23" rack with add-on ears and a wiring box (Figure 10).
017-241-B0 Rev B 21 88.1 3.47 76.2 3.00 FXM 350 w/RACK MOUNT KIT CONFIGURED FOR A 23" RACK & OPTIONAL EXTERNAL DRY CONTACTS MODULE TYP. 6.35[0.250] X 9.53[0.375] OBROUND THRU Figure 11 — FXM350 with ears for rack mounting 482.5 19.00 465.1 18.31 FXM 350 w/RACK MOUNT KIT CONFIGURED FOR A 19" RACK & OPTIONAL EXTERNAL DRY CONTACTS MODULE 584.1 23.00 566.7 22.31 43.7 1.72 46.0 1.
3.4 Options for Communicating with the FXM There are several ways to communicate with the Alpha FXM UPS: 1. The control panel page 42). 2. Window®’s HyperTerminal or other terminal emulation program to access the UPS command line system over the USB interface (page 76). 3. Alpha UPS Monitor installed on your computer and connected to the FXM over the USB interface . The Alpha UPS Monitor software can be downloaded from www.alpha.ca./downloads/. 4.
4. Unpacking the Equipment 4.1 Alpha FXM350/Micro350 Configuration The Alpha FXM is factory installed inside the Micro350 prior to shipping. WARNING! The Alpha FXM350/Micro350 combination is heavy, up to 12 kg (26 lb). Use proper lifting techniques. 4.2 Unpacking 1. Select a suitable area for unpacking. 2. Store all the packing material and boxes for possible equipment returns. 4.2.1 1. FXM350 Standalone or Micro350 (XL) Check the contents in your product package.
5. Installation WARNING! To avoid personal injury or damage to the equipment, always use at least two installation personnel to remove the unit from its container. 5.1 Installation of the Micro350 WARNING! Batteries or other components (with the exception of factory-installed components) must not be installed until the Micro350 cabinet has been securely set in place at its permanent location.
5.1.1.2 1. Procedure: Using the mounting bracket as a template, drill 2 holes into the pole to accept the machine bolts. 2. Secure the mounting bracket to the pole with the machine bolts as shown in Figure 13. 3. Secure the Micro350 cabinet to the mounting bracket with the supplied bolts (Figure 14). Front Side Wood Pole Figure 13 — Mounting to a wooden pole a. Hook the top of the mounting bracket under the case’s attachment fitting. b. Secure the cabinet to the mounting bracket.
5.1.1.3 Mounting to a Steel or Concrete Pole Have the following tools and materials on hand: • 13 mm nut driver for the bolts that attach the cabinet to the mounting bracket. • Two pole mount straps that fit the pole. Straps must be stainless or galvanized. • C001 Band-It tool or equivalent. • C206 3/4 inch stainless steel Band-It band or equivalent. • C256 3/4 inch stainless steel Band-It buckles or equivalent. Procedure: 1. Secure the mounting bracket to the pole with the straps.
5.1.1.4 Mounting to a Wall Have the following tools and materials on hand: • 13 mm nut driver for the bolts that attach the cabinet to the mounting bracket. • Four 1/4" x 1-1/8" lag bolts. • Four 1/4" diameter flat washers. • Drill with 1/8" bit for drilling pilot holes. • Assorted sockets and wrenches.
5.1.2 Wiring the Micro350 WARNING! Before starting, disconnect the Line power. If stranded wires are used for connection at the input terminal block, ferrules or equivalent crimping terminals must be used. Separate the AC input power cables from the output power cables within the Alpha FXM enclosure. Route them through separate conduit openings in the enclosure. Separate the DC Battery cable from the AC Input and Output power cables. Route the cable through its own opening.
5.1.2.1 1. Procedure Remove the front cover of the enclosure – lift the cover up and then pull out at the bottom. 2. If necessary, remove the knockouts with a hammer and screwdriver. 3. If used, install conduits into the openings. 4. Install the wires into the cabinet. Make sure that the wiring is long enough to reach the terminal blocks. Factory installed ground wire. 5. Strip the ends of the wires by 7/16" (11 mm). 6. Run the ground wire to the ground terminal shown in Figure 17. 7.
5.1.3 Options If applicable, connect the following—see Figure 3 on page 13. • USB cable • Dry contact alarms • User inputs 5.1.4 Ferrite Ring for Network Cable Remove the ferrite ring and cable tie from the plastic bag of small parts that were part of your shipment. Attach the ferrite ring to the connector end of your RJ45 network cable as shown in Figure 19. Figure 19 — Ferrite ring installed on RJ45 network cable 5.1.
5.2 Mounting and Wiring the FXM350 as a standalone device 5.2.1 Mounting The FXM 350 UPS module, which is approximately 13.5 in wide, can be mounted in several ways: • Wall mounted, with front access onto a 19" mounting tray that includes a battery cabinet • 19" or 23" rack mounted (with the addition of the optional ears shown in Figure 20). The signal assembly option provides additional user inputs and dry contacts.
5.2.2 Wiring the AC Input and Output WARNING! Make sure the line power is off and tagged. Switch off all input and output circuit breakers on the FXM350 before making any electrical connections. The electrical connectors are located on the right side of the FXM350. AC Input – 120/230Vac (#14 AWG) AC Output 2 – 24Vac (#12 AWG) Ensure that the cables are routed through the AC cover plate and/or wiring box and suitably strain relieved.
5.3 Wiring the External Batteries and Optional Battery Heater Mats WARNING! The batteries must be installed by qualified personnel trained in the safe use of highenergy power supplies and their batteries. Refer to the safety section in this manual. • Use new batteries when installing a new unit. Verify that all batteries are the same type with identical date codes. • Use appropriate battery voltage string for 24 and 48V versions of the products.
CAUTION! Torque the battery terminals according to the manufacturer’s specifications as given on the name plate or data sheet. 4. Place the batteries into the enclosure. Orient them so that connecting cable lengths are minimized. 5. If the optional battery restraining bar is used, install it as shown in Figure 23. 6. Connect the batteries as shown in Figure 22. If used, install the in-line fuse. 7. If the Micro XL or XL3 is used, connect and install the extra shelves of batteries. 8.
5.4 1. Start-Up Switch on the FXM battery circuit breaker. The LCD displays STANDBY. 2. Switch on the AC utility breaker at the main power panel. Switch on the AC Input circuit breaker on the FXM. If qualified, LINE appears on the LCD. 3. Allow the batteries to charge for approximately 8 hours. 4. The load should be receiving power, If not, perform troubleshooting.
6. Theory of Operation 6.1 Block Diagram Figure 24 shows the eight PCBs in the FXM350 and the communication path between them. AC INPUT & OUTPUT LINE FREQUENCY TRANSFORMER DC INPUT DC EMI BOARD MAIN BOARD 132 120 AC EMI BOARD 120 108 INV HEATER MAT OUTPUT HEATER MAT RELAY BOARD COMM MODULE N MICROCONTROLLER BOARD DRY CONTACTS BOARD USER INTERFACE LCD DISPLAY DRY CONTACTS & EXTERNAL SIGNALS OUTPUTS AND USER & BATTERY TEMPERATURE INPUTS Figure 24 — FXM 350 block diagram 6.
6.2.1 Line Mode AC EMI 132 Input 120 Grid relay Output(s) 120 108 INV Inverter/ Charger N Battery In line mode, the voltage input equals the voltage output. The FXM350 has Automatic Voltage Regulation (AVR) to maintain the output voltage within the regulation range. 6.2.1.1 Boost Mode When the input voltage drops, a reduction in output voltage is prevented by increasing the ratio of primary to secondary windings in the transformer.
6.2.1.3 Battery Charging in Line Mode The battery charging path is shown in Figure 25. • Charging current of 4A for 48V battery • Charging current of 6A for 24V battery • No de-rating of load on AC outputs AC EMI 132 Input 120 Grid relay Output(s) 120 108 INV Inverter/ Charger N Battery Figure 25 — Battery charging in line mode 6.2.2 Back Up (Inverter) Mode The FXM350 provides back up power from the batteries if utility power fails.
6.2.3 Standby Mode The FXM350 displays STANDBY when the DC breaker is closed (unit is ON), but no AC is present. When the AC input circuit breaker is switched on and line power is qualified, the Alpha FXM switches to LINE mode. If AC is within specifications, the FXM provides automatic voltage regulation (AVR). 6.2.4 Shutdown Mode The FXM/Micro350 can be shut down by switching off the AC breaker and the DC breaker.
7. Operating the FXM350 7.1 Switching the Alpha FXM On and Off Under normal operation, the Alpha FXM is always powered ON to supply uninterruptible power to the load. Switching off the Alpha FXM will disconnect the power supply to the load. If for any reason you need to switch off the Alpha FXM while maintaining power to your critical load, make sure that you have a plan that provides an alternate source of power. 7.1.1 1. Switch Off Procedure Switch off the AC input circuit breaker. 2.
7.1.4 Switching the Alpha FXM from Standby mode to Inverter mode When AC is not present and the loads need AC Power, the Alpha FXM can be forced to output AC using energy from the batteries. To force the inverter on, refer to the CONTROL MENU, shown in Figure 28, and INVERTER in Table B. 7.1.5 Switching the Alpha FXM from Inverter mode to Line mode The Alpha FXM remains in the Inverter mode for as long as the input circuit breaker is switched off.
7.2 Operating from the Control Panel Interface The LCD control panel provides “at a glance” monitoring. This panel, when used along with the CANCEL, SCROLL and SELECT buttons, allows you to program, make measurements, and troubleshoot the Alpha FXM350. Figure 27 shows the layout. The Alpha FXM350 is monitored and controlled with a series of menus and submenus. The Menu Tree is shown in Figure 28.
7.2.1 Operating Modes The Alpha FXM operating mode, (see Table A) automatically changes as a result of changes in the line. Refer to Chapter 10, Specifications, for Boost/Buck/Line transfer thresholds. The LCD panel automatically updates to reflect the change. Table A — UPS Operating Modes LCD display SHUTDOWN LINE BOOST1 BUCK1 INVERTER RETRAN TRAN STANDBY BYPASS 017-241-B0 Rev B Description The Alpha FXM inverter is switched off. Line power is disconnected from the load. The Alpha FXM is switched on.
Logo Screen (Figure 27) CANCEL Starting at the Logo Press the SCROLL button to move between the menus. Screen, press the SELECT button to go down one level. The SCROLL button moves only in one direction and is looped within a submenu, so if you scroll past your selection, continue to press the scroll till you reach it again.
7.2.2 The LCD Control Menu The control menu (Table B) lets you operate the Alpha FXM or program it to suit your operating conditions. 7.2.2.1 1. Procedure From the Logo screen press the SELECT button to go down to the CONTROL menu. 2. Press the SELECT button to enter the submenu (Table B). 3. Press the SCROLL button to move between items in the submenu. 4. When you have reached the item you want to change, press the SELECT button. The item chosen will blink. 5.
Table B — Control Menu LCD display FUNC MODE VOLTAGE Meaning Description Functional Mode This function toggles between: AUTOMATIC VOLTAGE REGULATION (AVR): The buck and boost modes are active. OR: QUALITY: The buck and boost modes are switched off, the input voltage is the Alpha FXM output voltage. Voltage Lets you set the Alpha FXM output voltage setting to 120 Vac or 230 Vac.
7.2.4 Making Measurements The System Status menu lets you make measurements of various Alpha FXM inputs, outputs, temperatures and other values. 7.2.4.1 1. Procedure From the Logo screen go to the SYSTEM STATUS menu. 2. Press the SELECT button to enter the submenu (Table C). 3. Press the SCROLL button to move between items in the submenu. When you reach the item you want to measure, stop pressing the button. The measurement is automatically displayed on the LCD. It is automatically updated every 0.
7.2.5 Viewing the 200-event Log Using the LCD display, or web interface, you can view up to the last 200 events the Alpha FXM went through and the malfunctions that triggered each of them. If more than 200 events occurred, the oldest is overwritten. To clear this log, see “Operating the Alpha FXM, INV RECORD.” To view the events on the LCD display, refer to the following procedure. 7.2.5.1 1. Procedure From the Logo screen, navigate to the EVENT STATUS MENU. 120/60/N LINE EVENT STAT MENUS 2.
7.3 Operating via the FXM Communication Module (Intranet or Internet) The internet or a company intranet can be used to communicate with the Alpha FXM through the factoryinstalled FXM communication module. In addition, the Alpha FXM can be monitored and controlled via a web browser or with SNMP protocols. B C A D A Screen selection menus B Current UPS operating mode. Updates automatically.
7.3.1 Installation and Set Up The following tools and materials are needed: • Computer with network card and web browser • Cross over cable or hub • The UPS Final IP Address and Subnet Mask and if needed the Default Gateway and the DNS Server addresses CAUTION! To successfully complete this procedure, you should have a working knowledge of network protocols and how to configure them. Consult your network administrator for details.
7.3.2 UPS Specifications This screen displays the Alpha FXM350 specifications.
7.3.3 UPS Monitoring These read-only screens show the Alpha FXM current input and output values and other measurements. 7.3.3.1 UPS Monitoring > Input & Output Shows the current line input and Alpha FXM output values and the Alpha FXM present operating mode. NOTE: Voltage 2 and Current 2 are the output voltage and current of the 24 VAC output. Figure 32 — Web GUI: Input & Output screen 7.3.3.
7.3.3.3 Monitoring > Relay & Load Shed Shows how the front panel dry contacts are configured. If any relays are used for load shedding, the time setting is shown. Available with optional additional dry contacts. C6 is not available with this model. Figure 34 — Web GUI: Relay & Load Shed screen 7.3.3.4 Monitoring > User Input Status Shows the current status of the user programmable inputs 1 to 4.
7.3.4 UPS Maintenance Menus Use the UPS Maintenance screens to configure and adjust the Alpha FXM to meet your operating needs. To change parameters, either click the On/Off buttons or select an item from a drop down menu. To execute the changes, click on the Update Configuration button. 7.3.4.1 UPS Maintenance > Unit Configuration 7.3.4.2 Sets the name, input, output and how often the Alpha FXM parameters update. Figure 36 — UPS Maintenance: Unit Configuration screen 7.3.4.
Table D — List of Parameters Maximum battery charging current Temperature compensation of battery charging Property settings of programmable user input #1 Action #1 setting of programmable user input #1 Action #2 setting of programmable user input #1 Property settings of programmable user input #2 Action #1 setting of programmable user input #2 Action #2 setting of programmable user input #2 Property settings of programmable user input #3 Action #1 setting of programmable user input #3 Action #2 setting of
7.3.4.4 UPS Maintenance > Battery: Allows adjustments of battery string voltage, charging parameters, low battery warning setting, periodic self test time, and starts the self test. Figure 38 — UPS Maintenance: Battery screen An accurate battery runtime estimation requires adjustment of the following parameter: • Peukert Number: Refer to Appendix A for calculation of the Peukert number to enter here. • Battery Capacity: This is the rated capacity (Ah) of the battery shown on the battery data sheet.
7.3.4.5 UPS Maintenance > Inverter: Turns the inverter on or off to start or stop backup battery power to the load.
7.3.4.6 UPS Maintenance > Relay & Load Shed: The Alpha FXM has 2 dry contacts (C1 and C2) on the front panel which can be configured by the user to open or close based on the specific trigger conditions. C3 to C5 are available with optional additional dry contacts. See Table J for a description of all available dry contact functions. See Table J for a description of all available dry contact functions. C3 to C5 are available with optional additional dry contacts.
Programmable Dry Contact Time of Day Action You can assign a dedicated timer to a dry contact. Upon entering the Inverter operating mode, the timer is activated and begins to count down from a user defined value. When the timer reaches zero, the programmed dry contact relay is activated (Status = ON).
You can define up to 2 peak time periods of the day in the Maintenance > Relay & Load Shed screen: 1. In the Time of Day Action Configuration dialogue box, set up the start and end time of the first rush hour under Time Period 1 and the second rush hour under Time Period 2. In this example, during the first time period (7 AM to 9 AM), all 3 timers are disabled (they do not count down at all). Similarly, all timers are disabled during the second time period (3 PM to 6 PM). 2.
Controlling the external fan with a temperature triggered dry contact The Temperature trigger has a user configurable range of +20°C to +55°C (68 – 131°F). When the battery temperature (monitored by the Battery Temperature Probe) reaches the threshold, the assigned relay energizes. The relay de-energizes when the temperature drops 10°C (18°F) from the Set temperature. This relay can be used to turn on the external fan.
7.3.4.8 UPS Maintenance > Time & Date: used to set the Alpha FXM date and time. Figure 47 — UPS Maintenance: Time & Date screen 7.3.4.7 UPS Maintenance > Password: used to reset the Alpha FXM password, which is limited to 4 alphanumeric characters. The factory set password is 1111.
7.3.4.9 Maintenance > User Input Two programmable user inputs are available as well as two optional user inputs. They can be user-configured similar to the dry contact relays. Supported functions include: (a) Shutdown, (b) User Alarm and (c) Self Test. Any user input can be configured to perform a certain action in response to different trigger types and logic levels.
5. Select User Alarm On from the Action #1 drop down menu. Figure 51 — User Input Configuration: Setting an Action 6. Click the Update Configuration button and enter the password to confirm if required. 7. Check the User Input Current Status at the UPS Monitoring > User Input Status page. Figure 52 — User Input Current Status Perform a quick test by shorting the User Input 1 to SC (ground) with a short length of PVC insulated electronic wire. The Alpha FXM should issue a User Input Alarm .
7.3.5 Event Manager 7.3.5.1 Alarms & Faults This read-only screen shows the operating status of the Alpha FXM. When the fault or alarm indicators on the horizontal bar are illuminated, place the mouse cursor over the light to display the context sensitive message. Figure 54 — Alarms & Faults screen 7.3.4.10 Event History This screen shows the last 200 events recorded by the Alpha FXM.
To view all the events, click All Events to open the Event Log Monitor window. Clicking on the Clear History button clears the log. This action cannot be undone. Figure 56 — Event Log Monitor screen In the Event Log Monitor window, the events are displayed by date and time. Scroll up and down the list to select the events you want to see. To download the latest events from the Alpha FXM click on the Get Events button. This process may take a few minutes.
To build a complete history of events for an Alpha FXM save all the downloaded events from the unit to the same event file. A maximum of 200 events can be stored on the Alpha FXM The oldest events are replaced by the newest ones. However, saving to the same event file gives the option of appending to an existing event file when selecting File > Save As.
To upgrade the Communication module, browse to the .ezip file and click OK to start the upload. This may take a few minutes to complete. Figure 59 — Upgrade Communication Module 7.3.7 Configure Site Information This screen is used to enter site location information into the UPS memory.
7.3.8 7.3.8.1 Communications Configure TCP/IP See section 7.3.1. 7.3.8.2 Configure SNMP Configure SNMP is used to set the UPS for use with SNMP communications. Figure 61 — Configure SNMP screen 7.3.8.3 Email Notification Email Notification tells the card to send an e-mail message whenever selected UPS events happen.
7.3.8.4 Test Email The Test Email feature tests the operation of the email notification option. Mail server settings can be tested as well. 1. Select Communications > Test Email. 2. If settings have already been saved with the Email Notification option, they will appear under: • Test Email Server Settings (with a check mark next to Same as Email Notification) and • Test Email Destinations 3. If necessary, modify the mail server settings and press the Update Configuration button to save the settings.
7.3.9 Keep Alive Activation of the Keep Alive feature provides a method to restore communications when a communication failure is detected. A reset temporarily removes power and resets the local communications equipment powered by this unit.
7.3.9.1 Keep Alive status/manual control: a. The Status field allows the user to enable or disable the Keep Alive function. (When disabled, the alarm is cleared.) When the function is On, the Current column displays the status: • Startup Delay • Pinging • Ping Echo Received • Timeout total_number_of_retries/current_retry_number • Reset total_number_of_retries/current_retry_number • Reset Complete • Failure • Failure: Startup Delay • Failure: Pinging b.
7.4 The Alpha UPS Monitor Interface The Alpha UPS Monitor graphical user interface (GUI) provides web or Windows-like computer communications with the Alpha FXM. The Alpha FXM can be connected to a computer with a USB cable. The screen and its features, shown in Figure 29, are used to monitor, control and set various parameters like the date and time, determine when to perform a weekly self test, change the relay configurations, etc. The on line indicator (F) shows if you are connected to the Alpha FXM.
7.4.1 Installation and Set Up of the Alpha UPS Monitor The following tools and materials are required: • Alpha UPS Monitor, available for download from www.alpha.ca./downloads/ • Windows 2000 or later with Microsoft .NET framework installed • USB computer cable 7.4.1.1 1. Checking Your Windows Computer for the .NET Framework Click on the Start button. 2. Go to and click on Settings. 3. Click on Control Panel. 4. Double-click on the Add or Remove Programs icon. 5. Scroll through the list of applications.
7.4.2 Alpha UPS Monitor Functions Alpha UPS Monitor interface is similar to the Web interface. Refer to the corresponding heading in section 7.3.
7.5 HyperTerminal Interface The Alpha FXM front panel has a USB connector. When connected to a PC with Windows® HyperTerminal or other terminal emulation software, the Alpha FXM can be remotely monitored and controlled with the HyperTerminal command-line system. HyperTerminal is a Windows application that helps to connect your computer to other remote computers using one of the USB com ports. The FXM350 has a USB port, not an RS232 port.
7.5.2 Main Menu Screen Once HyperTerminal is open, ensure that the FXM has connected to the computer. See Figure 67 for connection indicators. The main menu screen shows the Alpha FXM current input and output values, displays any faults or alarms and gives access to the submenus. The Alpha FXM is controlled by submenu 3. To access a particular submenu, type in the submenu number and press Enter. To update the main menu screen, press Enter. The complete menu tree is shown in Figure 67.
7.5.2.1 Main Menu Screen — Submenus Submenus #1, 2 and 4 are read-only screens for monitoring the Alpha FXM. To control the Alpha FXM, use submenu #3, the Maintenance submenu. 0-Main Menu Submenus 1-Unit Specifications Unit Model Submenus 2-Input/Output Values Input 3-Maintenance 4-Line Slow Detection Setup 30-Battery Test Options This read-only screen shows the Alpha FXM input voltage parameters. These values are factory set and cannot be changed in the field.
7.5.2.2 Main Menu Screen — Line Status Line status line reports the line condition. For an updated value, press Enter. Table E — Line Status (see Figure 67) Normal The line is within specifications. See specifications, “Boost/Buck/Line Transfer Thresholds”. The Alpha FXM is operating in Line mode. Boost Line voltage is out of tolerance. The Alpha FXM is operating in Boost mode. Buck Line voltage is out of tolerance. The Alpha FXM is operating in Buck mode. Blackout The line is absent.
7.5.2.4 Main Menu Screen — Fault and Alarm Displays Faults and alarms display on the main menu screen. See Chapter 9, Troubleshooting. Table G — Faults (see Figure 67) Short_Circuit The load has a short. Vout_Hi The output voltage is above specifications. Batt_Hi The batteries cannot be charged. Batt_Lo The batteries are almost discharged. Vout_Lo The output voltage is below specifications. Overload The Alpha FXM is overloaded. Remove excess loads.
7.5.3 Adjusting and Controlling the Alpha FXM Use submenu #3, the Maintenance submenu (Figure 67 and Figure 68) to control the Alpha FXM and change selected items to meet your operational needs. 7.5.3.1 From the Main menu, type 3 and press Enter. Table I — Maintenance Submenu 30 Battery Test Options Starts the battery test and sets how long the test will run. The default setting for the test depth-of-discharge is 20%, but this can be adjusted from 0 to 100%.
7.5.4 Programming the Dry Contacts The Alpha FXM front panel contacts (C1 and C2) can be programmed to meet your specifications. In addition, C3 to C5 are available with optional additional dry contacts as well as two optional user inputs 3 and 4. Each contact can only be programmed for one function at a time and cannot show multiple conditions. The functions of dry contacts can be changed with HyperTerminal.
7.5.4.1 Setting the Timer Contact Interval If you configure one of the dry contacts to act as a timer, the next step is to set the value of the timer. Time can be entered in units of 0.5 second; e.g. 120 units of 0.5 seconds = 60 seconds. However, it is more intuitive to enter time in the hh:mm:ss format, such as 00:01:00 for 1 minute or 60 seconds. Both methods are shown in the following example.
7.5.4.2 Controlling the external fan by temperature triggered dry contact The Temperature trigger has a user configurable range of +20°C to +55°C (68 – 131 °F). When the battery temperature (monitored by the Battery Temperature Probe) reaches the threshold, the assigned relay closes and turns on the external fan. 1. Assign the Temperature trigger function to an available dry contacts, (for example, c2=11, where 11 is the assigned index for the Temperature trigger function.) 2.
7.5.5 Setting the Date and Time Table L — Setting the Date and Time Enter command UPS display Description clock and press Enter *clock=12/31/07 22:00:00 clock=010111 120000 and press Enter *clock=01/01/11 12:00:00 † Returns the current date and time. Sets the date and time to Jan 01, 2011, 12:00 pm Notes: 1. Time is displayed in the 24 hours clock format. 2. Changing the mm/dd/yy format with DATE SEL on the LCD Control menu does not change the USB mm/dd/yy format. 3.
7.5.6 Viewing the Serial Number To display the serial number of the Alpha FXM UPS, type "∗QY0" at the command line and press "Enter". 7.5.7 Setting the Peukert Number and Capacity You can set the Peukert Number and Capacity using the USBinterface or the web interface. To display the current Peukert Number, type "∗QY6" at the command line and press "Enter". To change the Peukert Number to 1.1345, type "∗ST6:1.1345" at the command line and press "Enter".
7.5.8 200-event Log Up to 200 events are stored in the Alpha FXM log. If more than 200 events occur, the oldest is over-written. 7.5.8.1 Procedure 1. To see the log, type event (all lower case) and press Enter. The events are listed starting with the most recent and appear as: eventX=12/25/99 01:45:59 0000000000000000, 0000000000000000, 000 Event Date Time Alarm Fault Mode Date & Time formats depend on selected display format See below for details on these readouts.
7.5.9 Restoring All Parameters to Default Values The purpose of this command is to reset the Alpha FXM to the factory default state. See Table D for a list of parameters that will be restored to their default values. CAUTION! This command resets all parameters that are user-configurable. All previously programmed operation will be lost. Implement a backup plan for mission critical operations. This command is password protected. 7.5.8.2 88 Procedure 1. Type default:all and press Enter. 2.
8. Maintenance 8.1 Updating the Software The Alpha FXM firmware can be reinstalled or updated to the latest version with this procedure. If your Alpha FXM is provided with the factory-installed FXM communication module, the firmware upgrade can be done via an intranet or internet connection. You will need the following items: • USB connection cable to the Alpha FXM • uBug12 software must be installed. It is available for download at www.alpha.ca\downloads.
6. In the uBug12 screen, type (all lower case) fbulk and press ENTER. The erasing pop-up appears. It disappears when the Alpha FXM memory is erased. If an error message appears, send the fbulk command again. 2: Erasing pop-up appears 1: Type fbulk 7. In the uBug12 screen, type (all lower case) fload(1 space);b and press ENTER. A pop-up appears asking you to locate the new firmware. Look for a .sx record (*.sx). Select this new firmware. The fload pop-up appears. 2: Look for .
8. When the software has finished loading into the Alpha FXM, a pop-up shows “Loaded OK in (xx) seconds.” If an error message appears, switch off the Alpha FXM and start over. It should not take more than one or two restarts to load the software. If the problem persists, contact Alpha technical support. Firmware is loaded 9. Type (all lower case) exit and press ENTER. The uBug12 screen disappears. 10. Switch off the battery breaker. 11.
8.2 8.2.1 Testing and Replacing the Batteries Battery Life Batteries lose their ability to store power as they age. Regularly test the batteries to ensure that they can continue providing reliable service. Battery life is reduced by three major factors: • Temperature – higher ambient temperatures, especially above 25°C (77°F), will reduce battery life. For example, an average operating temperature of 27°C (81°F) will likely reduce the life of the battery by 25%.
8.2.3 Battery Maintenance The batteries supplied with this unit are sealed and maintenance free. Regularly ensure that all connectors are tight and free of corrosion. The presence of corrosion, swelling of the battery case, or distortion in the shape of the case suggests that the batteries need to be replaced. 8.2.4 1. Battery Conductance Test (Optional) Place the conductance meter probes across Battery #1. 2. Record the voltage and Siemens values in a log book. 3. Repeat for batteries #2, #3 and #4.
WARNING! Read and understand the battery safety instructions in “Product Safety Information”. CAUTION! Make sure all the replacement batteries are of the same type and rating. Failure to do so could result in improper charging and damage to the batteries. The Alpha FXM cannot provide backup battery power while the batteries are being replaced. If the line becomes unqualified while the batteries are being replaced, the Alpha FXM shuts down and no power is provided to the load. 8.2.5.2 1.
8.3 Preventive Maintenance Perform preventive maintenance on the Alpha FXM module every 6 to 12 months. For mission critical applications such as backup for traffic intersections, more frequent maintenance should be done. Proper implementation of the following procedure will insure that your system continues to provide reliable backup power in the event of a utility power failure. 8.3.
9. Troubleshooting When the front panel alarm LED is illuminated or flashing, the Alpha FXM has a malfunction: • Red LED solidly illuminated indicates a fault in the Alpha FXM. (See Table P.) • Red LED flashing indicates an alarm. ( See Table O.) The web interface can also be used for troubleshooting. 9.1 Procedure 1. Press the SELECT button. 2. The LCD may display one or more of the conditions in Table O. 3. Press the SCROLL button to see if more than one malfunction is present. 4.
Table P — Fault Submenu LCD Shows Problem Description Overload Fault Short Circuit Intl Temp Fault Output Over Voltage Output Voltage Low Battery Fail What To Do The load draws more power than the Alpha FXM can provide. This can lead to an automatic Alpha FXM shutdown. Remove excess loads. The load has a short. Check the output. Remove the faulty load if necessary. The Alpha FXM internal temperature is too high and could cause an automatic Alpha FXM shutdown.
10. Specifications Table R — Mechanical Specifications Parameter Value Dimensions H x W x D in (mm) Weight without batteries lb (kg) Color FXM350: 5.22 (133) x 15.5 (394) x 8.75 (222) Micro350 Std: 19.7 (500) x 14.1 (358) x 11.6 (294) Micro350 XL: 30.6 (776) x 14.1 (358) x 11.6 (294) Micro350 XL3: 52.4 (1330) x 14.1 (358) x 11.6 (294) FXM350: 19 (8.62) Micro350 Std: 43.4 (19.7) Micro350 XL: 49.8 (22.6) Micro350 XL3: 69.2 (31.
Table S — Electrical Specifications Parameter Value INPUT Voltage (nominal), Vac Frequency, Hz, ±5% 120 or 230 60/50 (auto-detection), Output frequency = Input frequency Current, Amps (@ nominal Vin and max battery charging current) FXM 350-24: 5.3 / 2.7 @120/230 Vac FXM 350-48: 5.7 / 2.9 @120/230 Vac AC Input Circuit Breaker Ratings, Amps FXM 350-24: 7 / 3.5 @120/230 Vac FXM 350-48: 7 / 3.
Table T — Boost/Buck/Line Transfer Thresholds Parameter Value 120 Vac Units 230 Vac Units High Line Transfer High Line Retransfer 152 Vac 146 Vac 282 Vac 272 Vac Buck 1 Transfer Buck 1 Retransfer 134 Vac 128 Vac 250 Vac 236 Vac Boost 1 Retransfer Boost 1 Transfer 116 Vac 112 Vac 210 Vac 207 Vac Boost 2 Retransfer Boost 2 Transfer 102 Vac 98 Vac 180 Vac 176 Vac Low Line Retransfer Low Line Transfer 97 Vac 88 Vac 162 Vac 151 Vac Table U — Regulatory Parameter Value Electrical Safety UL 1778
11. Warranty Alpha Technologies Ltd. warrants all equipment manufactured by it to be free from defects in parts and labor, for a period of two years from the date of shipment from the factory. The warranty provides for repairing, replacing or issuing credit (at Alpha’s discretion) for any equipment manufactured by it and returned by the customer to the factory or other authorized location during the warranty period. There are limitations to this warranty coverage.
12. Emergency Shutdown Procedure The Alpha FXM UPS contains more than one live circuit. In an emergency, line power may be disconnected at the UPS’s input, but AC power can still be present at the output. 1. Switch OFF the input circuit breaker. 2. Switch OFF the battery circuit breaker. 3. Disconnect the AC input power. 4. Disconnect the battery string. 11.1.3.
Appendix A - Puekert Number and Battery Capacity A.1 Introduction The Alpha FXM series UPS units run on batteries when the AC utility power fails. In this mode, the user may want to estimate the remaining time that UPS batteries can supply power to the loads. The battery run time remaining is calculated based on the Peukert equation. Two critical parameters are required for the equation: • Peukert number. • Peukert capacity. The Peukert number and Peukert capacity depend on the battery characteristics.
A.4 Example The following example shows how to calculate Peukert’s number and capacity from a configured battery string. Consider four Alpha 180GXL batteries connected and configured as shown in the figure below. Two of the four batteries are connected in series, and the two series strings are connected in parallel to the 24 V DC output.
A.5 Using the Spreadsheet Download the spreadsheet “Peukert’s Parameters Calculator.xls” from www.alpha.ca website. Enter the Battery voltage and nominal load } From the data sheet of the batteries enter the 2 closest currents and discharge hours Enter the number of parallel strings CAUTION! The battery runtime is only an estimation and must not be relied on for critical applications. The battery runtime remaining is applicable only in inverter/backup mode.
Appendix B - Types of Triggers There are 3 types of trigger: B.1 Edge trigger When the user input changes from one state to the other, the Alpha FXM is triggered to perform Action #1. If the level is set to High, the action will be triggered by a Low to High edge (leading edge). If the level is set to Low, the action will be triggered by the High to Low edge (falling edge).
Level Alternative When the level is set to High, the Alpha FXM is triggered to perform the next action when the user input changes from Low to High. If the input then changes from High to Low, no action will be triggered because the level is set to High. In other words, only a Low to High user input level triggers an action when Level is set to High. Similarly, when Level is set to Low, the Alpha FXM will trigger an action only with a High to Low user input.
Alpha Technologies Ltd. 7700 Riverfront Gate Burnaby, BC V5J 5M4 Canada Tel: +1 604 436 5900 Fax: +1 604 436 1233 Toll Free: +1 800 667 8743 Alpha Technologies Inc. 3767 Alpha Way Bellingham, WA 98226 United States Tel: +1 360 647 2360 Fax: +1 360 671 4936 Alpha Industrial Power Inc.