6.10 Hardware
This menu category consists of output relay configuration and testing. See also 6.6.3.1 for an overview.
6.10.1 Configure Relays
6.10.2 Test Relays
From this menu the Supervisor can toggle the state of a relay to verify its condition. Change of state is
temporary as all relays return to their default states after leaving this menu. (Note, the web interface is
similar in operation: Main Menu > Hardware > Test Relays)
6.10.3 Test Modem (Web Interface only)
See Table C.
Figure 111 — Configure Relays – LCD
Select relay then tap
Congure Settings
From the pop-up menu, tap Congure to set
email notication and/or SNMP dial out trap
notication.
Select Toggle Polarity to specify if the relay is
normally energized or normally de-energized.
2
3
1
Figure 112 — Configure Relays – Web
Set email notication and/or
SNMP dial out trap notication
and Severity.
Specify if the relay is normally en-
ergized or normally de-energized.
Select Relay
to test
Tap Toggle
State to test
selected item.
NOTE: A message of warning appears if toggling the
selected relay would affect the operation of an LVD
(web interface shown).
Discard changes
and return to
previous screen
Figure 113 — Test Relays – LCD