Table R Inverter Alarm Codes
Alarm Type Cause Solution
T2S Event
226 NO TRANSMISSION Alarm from the T2S - does
not see any TSI- all modules -
system alarm or when the T2S
does not see one of the modules
Replace defective inverter or adapt
conguration
227 DIG INP1 FAILURE Digital input has changed status Check device connected on input digital
228 DIG INP2 FAILURE Digital input has changed status Check device connected on input digital
229 REDUNDANCY
LOST 
Lost of inverter redundancy Replace defective inverter or adapt
conguration
230 REDUND + 1 LOST  Lost of inverter redundancy + 1 
inverter
Replace defective inverter(s) or adapt
conguration
231 SYS SATURATED Load of system greater than the 
preset value
Reduce load or add inverter on the system, or
change the alarm level trigger.
232 MAIN SOURCE
LOST
Priority source lost (depends
on the conguration AC/AC or 
Online)
1) In AC/AC conguration: Reconnect AC IN or 
check conguration or check live value. 2) In 
Online conguration: Reconnect DC or check 
conguration or check level voltage
233 SEC SOURCE
LOST
Secondary source lost (depends
on the conguration AC/AC or 
Online)
1) In ONLINE conguration: Reconnect AC 
IN or check conguration or check live value. 
2) In AC/AC conguration: Reconnect DC or 
check conguration or check level voltage
234 T2S BUS FAIL     The communication bus to T2S
has failed
Hardware problem. Replace T2S
235 T2S FAILURE      T2S has failed Hard ware problem. Replace T2S
236 T2S STARTED T2S has started
237 LOG CLEARED      T2S has cleared the log
238 CONFIG MODIFIED  Conguration is modied
239 NEW MOD
DETECTED
One more module is plugged
240 DATE & TIME MOD Date and time are modied
241 CFG READ IN MOD  T2S has read the CFG
242 LOG NEARLY FULL This item will be set as, No
alarm, Minor or major alarm. (see
conguration le)
Clear log le
243 T2S FLASH ERROR  Flash of T2S is corrupt and has
failed
Hardware problem. Replace T2S