Manual

129
0700015-J0 Rev B
Table Q Inverter Parameters
Submenu Item
Default Setting Units
AC : Fac_in Low Stop              47.0 Hz
AC : Fac_in High Start 62.7 Hz
AC : Fac_in High Stop 63.0 Hz
AC 1 : Vac_in Low Start           92.5 V
AC 1 : Vac_in Low Transfer        87.5 V
AC 1 : Vac_in Low Stop            87.5 V
AC 1 : Vac_in High Start 133.0 V
AC 1 : Vac_in High Transfer 138.0 V
AC 1 : Vac_in High Stop 138.0 V
AC 2 : Vac_in Low Start           92.5 V
AC 2 : Vac_in Low Transfer        87.5 V
AC 2 : Vac_in Low Stop            87.5 V
AC 2 : Vac_in High Start 133.0 V
AC 2 : Vac_in High Transfer 138.0 V
AC 2 : Vac_in High Stop 138.0 V
AC 3 : Vac_in Low Start           92.5 V
AC 3 : Vac_in Low Transfer        87.5 V
AC 3 : Vac_in Low Stop            87.5 V
AC 3 : Vac_in High Start 133.0 V
AC 3 : Vac_in High Transfer 138.0 V
AC 3 : Vac_in High Stop 138.0 V
AC 4 : Vac_in Low Start           92.5 V
AC 4 : Vac_in Low Transfer        87.5 V
AC 4 : Vac_in Low Stop            87.5 V
AC 4 : Vac_in High Start 133.0 V
AC 4 : Vac_in High Transfer 138.0 V
AC 4 : Vac_in High Stop 138.0 V