Table Q — Inverter Parameters
Submenu Item
Default Setting Units
Max power (pc of nominal power) 150 %
Max Overload Duration 15 s
Synchronisation Tracking Speed 0
Remote OFF disable ACin Power 0
Negative Power (0 : OFF 1 : ON) 1
External Clock (0 : NO 1 : YES) 0
OUT 1 : phase shift 0 deg
OUT 1 : Nominal Output Voltage 120.0 V
OUT 2 : phase shift 120 deg
OUT 2 : Nominal Output Voltage 120.0 V
OUT 3 : phase shift 240 deg
OUT 3 : Nominal Output Voltage 120.0 V
OUT 4 : phase shift 0 deg
OUT 4 : Nominal Output Voltage 120.0 V
OUT 5 : phase shift 0 deg
OUT 5 : Nominal Output Voltage 120.0 V
OUT 6 : phase shift 0 deg
OUT 6 : Nominal Output Voltage 120.0 V
OUT 7 : phase shift 0 deg
OUT 7 : Nominal Output Voltage 120.0 V
OUT 8 : phase shift 0 deg
OUT 8 : Nominal Output Voltage 120.0 V
DC 1 : Vdc_in Low Start 49.0 V
DC 1 : Vdc_in Low Transfer 42.0 V
DC 1 : Vdc_in Low Stop 42.0 V
DC 1 : Vdc_in High Start 61.0 V
DC 1 : Vdc_in High Transfer 62.0 V
DC 1 : Vdc_in High Stop 62.0 V
DC 2 : Vdc_in Low Start 49.0 V
DC 2 : Vdc_in Low Transfer 42.0 V
DC 2 : Vdc_in Low Stop 42.0 V
DC 2 : Vdc_in High Start 61.0 V
DC 2 : Vdc_in High Transfer 62.0 V