The inverter configuration file is actually one big file, but is presented here as Table P, Table Q, and Table R
for clarity.
Table P — Inverter Global Settings
Submenu Item
Default Setting Units
Number of module in phase 1 10
Number of module in phase 2 10
Number of module in phase 3 10
Number of module in phase 4 0
Number of module in phase 5 0
Number of module in phase 6 0
Number of module in phase 7 0
Number of module in phase 8 0
Amount of redundancy in phase 1 0
Amount of redundancy in phase 2 0
Amount of redundancy in phase 3 0
Amount of redundancy in phase 4 0
Amount of redundancy in phase 5 0
Amount of redundancy in phase 6 0
Amount of redundancy in phase 7 0
Amount of redundancy in phase 8 0
Number of DC input groups 1
Number of AC input groups 3
Table Q — Inverter Parameters
Submenu Item
Default Setting Units
Input Source (AC : 0 DC : 100) 0 %
ACin Mode (0 : normal 1 : Safe) 0
Walk-in Mode (0 : NO 1 : YES) 0
Number of phases 1
Mode (0 : star 1 : triangle) 1
Free running Frequency 60.0 Hz
Short Circuit Voltage Threshold 80 V
Short Circuit Hold Time 60.0 s
Booster 10xIin (0 : OFF 1 : ON) 1
Max current (pc of nominal curr) 150 %