Table L — Communications menu defaults
Submenu Item
Programmable Range Default Setting
IP Address Check = obtain automatically Not checked, 10.10.10.201
Subnet Mask 0.0.0.0 – 255.255.255.255 255.255.255.0
Gateway 0.0.0.0 – 255.255.255.255 10.10.10.1
Modem Rear Port Device Internal/External/NULL NULL
Baud Rate 9600 – 57600 baud 19200 baud
Enable Callback Check = enable Not checked
Modem Init String Consult factory A0 S1 B3 &F2
Craft Port Baud Rate 9600 – 57600 baud 57600 baud
RAS Client Settings Phone Number 64 characters maximum N/A
Login Account 64 characters maximum N/A
Domain Name 64 characters maximum N/A
Password 64 characters maximum N/A
Web Settings Routing Front Craft Port, Rear Modem, None Front Craft Port
SMTP Server Settings IP Address 64 characters maximum N/A
Send Domain 64 characters maximum N/A
From Address 64 characters maximum N/A
To Address 64 characters maximum N/A
Copy Address 64 characters maximum N/A
Table M — Hardware menu defaults
Submenu Item
Programmable Range Default Setting
Congure Relays (1–16) Energized/De-Energized De-Energized
Table N — Supervisor menu defaults
Submenu Item
Programmable Range Default Setting
Supervisor Access Code Energized/De-Energized De-Energized
0-9999999999 1234