11. Factory Ranges and Defaults
Table G Rectiers menu defaults
Submenu Item
Programmable
Range
Default Setting
12Vdc
24Vdc 48Vdc 125Vdc 220Vdc
Float (FL) Voltage 0-9999999999 13.50V 27.00V 54.00V 130.50V 229.5V
Equalize (EQ) Voltage 0-9999999999 13.75V 27.50V 55.00V 132.92V 233.75V
Battery Test (BT) Voltage 0-9999999999 11.50V 22.00V 44.00V 106.33V 187.00V
OVP 0-9999999999 14.25V 29.00V 57.00V 137.75V 242.25V
LVA 0-9999999999 11.00V
22.00V 44.00V 106.33V 187.00V
HVA
0-9999999999 14.00V
28.00V 55.50V 134.13V 235.88V
Current Limit (CL)
0-9999999999 100%
Power Limit (PL)
0-9999999999 100%
Equalize Timeout
0-9999999999 30 hours
Battery Test Duration
0-9999999999 8.0 hours
Slope (Adjust)
0-9999999999 1.00%
Backlight Timeout
0-32767 1 minute
Security Code
0-32767 123
Module Start Delay
0-32767 1 second
System Start Delay
0-32767 0 seconds
Soft Start Ramp Rate
Normal/Fast Normal
Temp Display Scale
Celsius/Fahrenheit Celsius
Current/Power Limit Alarm
Enable/Disable Disable
Remote Shutdown
Enable/Disable Enable
Local Access Alarm
Enable/Disable Enable
Ramp Test
Enable/Disable Enable
Power Save
Enable/Disable Disable
Redundant Rectiers
0-32767
1
Maximum Power Usage
0-32767
80%
Table H Converters menu defaults
Submenu Item
Programmable Range 24V–48V Defaults 48V–24V Defaults
Output Voltage 0-9999999999 54.00V 27.00V
OVP 0-9999999999 57.00V 28.50V
Input Voltage Shutdown 0-9999999999 21.0V 42.0V
Input Voltage Restart 0-9999999999 25.0V 50.0V
Start Delay 0-32767 1 second
Current Limit (CL) Alarm Enable/Disable Enable