Submenu Item Programmable Range Default Setting
12Vdc 24Vdc 48Vdc 125Vdc 220Vdc
LVD 1 0-9999999999 10.5V 21.00V 42.00V 101.50V 178.50V
LVC 1 0-9999999999 12.5V 25.00V 50.00V 120.83V 212.50V
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) 1
Control Check = enable LVD control Checked
Alarm cutoff Check = allow alarm to be cutoff Not checked
LVD 2 0-9999999999 10.5V 21.00V 42.00V 101.50V 178.50V
LVC 2 0-9999999999 12.5V 25.00V 50.00V 120.83V 212.50V
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) 2
Control Check = enable LVD control Checked
Alarm cutoff Check = allow alarm to be cutoff Not checked
LVD 3 0-9999999999 10.5V 21.00V 42.00V 101.50V 178.50V
LVC 3 0-9999999999 12.5V 25.00V 50.00V 120.83V 212.50V
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) 3
Control Check = enable LVD control Checked
Alarm cutoff Check = allow alarm to be cutoff Not checked
LVD 4-10 0-9999999999 10.5V 21.00V 42.00V 101.50V 178.50V
LVC 4-10 0-9999999999 12.5V 25.00V 50.00V 120.83V 212.50V
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) N/A
Control Check = enable LVD control Not checked
Alarm cutoff Check = allow alarm to be cutoff Not checked
LVD Inhibit (Status) Active/Inactive Inactive
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) N/A
Alarm cutoff Check = allow alarm to be cutoff Not checked
High Volt. Shutdown 0-9999999999 14.25V 29.50V 58.00V 140.17V 246.50V
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) N/A
Control Check = enable LVD control Not checked
Alarm cutoff Check = allow alarm to be cutoff Not checked
CEMF In-circuit Voltage 0-9999999999 13.70V 27.40V 54.80V 132.43V 232.90V
Bypass Voltage 0-9999999999 13.55V 27.10V 54.20V 130.98V 230.35V
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) N/A
Control Check = enable LVD control Not checked
Alarm cutoff Check = allow alarm to be cutoff Not checked
Table J–Controls menu defaults