Default is off m = 0 By enabling the m = 1 mutes the acoustic path at close relay
(1 or 2) in "electric lock" (modes 1 and 5). This feature is there because if you
often use code lock function or exit button, so the switch-on time to hear the tone
exchange. For some customers, this can be distracting.
This constant serves a purpose to identify the no.1 button in the composition of
the module. After entering the number of buttons s the button no 1 is moving so
it is always first.
Number of buttons on the main panel
s - choice
0
0
1
1
2
2
WARNING !! setting this parameter materially affects number dialling.
Parameter
Value
Meaning
Basic
6*
t
Delayed start for switchboards with line
testing (Siemens) (0/1)
0
This function is off as standard t=0. By switching this function on t=1 the
processor goes into sleep mode immediately after the line connection, and after
3 secs. The Brave initialises. The line connection after the power supply
connection is then delayed - state switching on/restarting of the switchboard. If
this function is not working and the telephone switchboard still identifies a line
fault, then there is no other option but to use an internal power supply, by
switching over DIP switch 3 and 4 to "on" – this is only possible with version (C).
This measure has the same use as the Best Box for older type of
communicators.
Parameter
Value
Meaning
Basic
6#
s
Setting of the number of buttons on the main
panel.
2
Parameter
Value
Meaning
Basic
68
b
Mute at the lock activated (0/1)
0