Specifications
016-538-B0-002 Rev. B
8
Fig. 1-3, Ferroresonant ‘Tank’ Circuit and Resulting Output Waveform
The base APX-100W unit contains a ferroresonant transformer, resonant circuit capacitor,
and an input/output terminal block.
The APX-100W uses ferroresonant transformer technology to provide line conditioning and
voltage regulation. The primary and secondary windings of the transformer are physically
isolated from each other by a large steel core which greatly reduces the capacitive coupling
of spikes and noise to the secondary winding. This provides a regulated, current-limited
output with excellent isolation and noise attenuation: 120dB in common mode; and 60dB in
transverse mode.
An oil-fi lled resonant capacitor is connected to the resonant (secondary) winding of
the transformer forming a tank circuit. This provides the resonant circuit function which
contributes to the voltage regulation of the supply. The advantage of this type of transformer/
capacitor design is the ability of the ferroresonant transformer to regulate its output voltage
over a wide range of input voltages and output loading. Typical output voltages may vary +
3% to 5%, with input voltage variations of + 15% of nominal line voltage, and output loading
of 20% to 100%. This tight regulation is advantageous in cable television applications as the
active devices are protected from dangerous voltage fl uctuations.
Another unique feature of the ferroresonant transformer is its ability to provide current limiting
in the event of a short circuit. This effect is called foldback. The transformer’s output current
can typically reach 150% of the nameplate output current rating for a short period of time
without damage to the transformer. When the transformer reaches the saturation point, the
output current will decrease (foldback on itself) to a minimum value, and thereby provide
current limiting. Designs based on a ferroresonant transformer are extremely rugged and
reliable, and offer many years of trouble-free operation.
1.0 Introduction, continued
1.1 Operating Principle
A true RMS voltmeter must be used to correctly measure the output voltage of the APX-100W .
NOTE:
T1
C1
Ferroresonant Transformer and
AC Capacitor
Clean Output Waveform
Noisy Input Waveform