User Manual
80
746-257-B5-001, Rev. A1 (11/2013)
Parameter OID Description Access Type Value
SYSTEM COUNTERS
atiBBSysViewCounters 1.3.6.1.4.1.926.1.4.1.1.4 Object Identier
atiBBSysViewSelfTestInterval 1.3.6.1.4.1.926.1.4.1.1.4.1.0 Power supply Self Test interval Read/Write Integer
atiBBSysViewSelfTestCountdown 1.3.6.1.4.1.926.1.4.1.1.4.2.0 Power supply Self Test countdown Read/Write Integer
atiBBSysViewSelfTestDuration 1.3.6.1.4.1.926.1.4.1.1.4.3.0 Power supply Self Test duration Read/Write Integer
atiBBSysViewInverterRuntime 1.3.6.1.4.1.926.1.4.1.1.4.4.0 Power supply inverter runtime Read Only Integer
atiBBSysViewStandbyEvents 1.3.6.1.4.1.926.1.4.1.1.4.5.0 Power supply standby events Read Only Integer
atiBBSysViewRuntimeRemaining 1.3.6.1.4.1.926.1.4.1.1.4.6.0 Power supply runtime remaining Read Only Integer
atiBBSysViewTimeInStandby 1.3.6.1.4.1.926.1.4.1.1.4.7.0 Power supply time in standby Read Only Integer
atiBBSysViewTimeSinceLastStandby 1.3.6.1.4.1.926.1.4.1.1.4.8.0 Power supply time since last standby Read Only Integer
SYSTEM LOGS
atiBBSysLogs 1.3.6.1.4.1.926.1.4.1.2 Object Identier
atiBBSysLogsEventsTable 1.3.6.1.4.1.926.1.4.1.2.1 Table of logged events Read Only
atiBBSysLogsCongTable 1.3.6.1.4.1.926.1.4.1.2.2 Table of logged conguration items Read Only
atiBBSysLogsPerformTable 1.3.6.1.4.1.926.1.4.1.2.3 Table of logged performance information Read Only
atiBBSysLogsBatteryTable 1.3.6.1.4.1.926.1.4.1.2.4 Table of logged battery information Read Only
SYSTEM APPLICATIONS
atiBBSysApps 1.3.6.1.4.1.926.1.4.1.3 Object Identier
atiBBSysAppsPsHealth 1.3.6.1.4.1.926.1.4.1.3.1 Object Identier
atiBBSysAppsPsHealthPsCount 1.3.6.1.4.1.926.1.4.1.3.1.1.0
Indicates the number of power supplies that support
health analysis
Read Only Integer
atiBBSysAppsPsHealthTable 1.3.6.1.4.1.926.1.4.1.3.1.2 Table - row for each power supply
atiBBSysAppsBattStatus 1.3.6.1.4.1.926.1.4.1.3.2 Object Identier
atiBBSysAppsBattTable 1.3.6.1.4.1.926.1.4.1.3.2.1 Table - row for each battery Read Only Integer
atiBBSysAppsBattStringNum 1.3.6.1.4.1.926.1.4.1.3.2.1.1.1 String that this battery is a member of Read Only Integer 1 to 4
atiBBSysAppsBattBatteryNum 1.3.6.1.4.1.926.1.4.1.3.2.1.1.2 Battery number in string Read Only Integer 1 to 4
atiBBSysAppsBattMfgDate 1.3.6.1.4.1.926.1.4.1.3.2.1.1.3 Manufacture Date, typically stamped onto battery Read/Write Octet String Date
atiBBSysAppsBattAge 1.3.6.1.4.1.926.1.4.1.3.2.1.1.4
Age of battery in months based on Manufacture
Date
Read Only Integer
atiBBSysAppsBattMhos 1.3.6.1.4.1.926.1.4.1.3.2.1.1.5 Measured Battery MHOs Read/Write Integer
atiBBSysAppsBattBalancing 1.3.6.1.4.1.926.1.4.1.3.2.1.1.6 Status of attempt to balance the battery Read Only Integer
1=balanced
2=inProgess
3=failed
atiBBSysAppsBattStringCount 1.3.6.1.4.1.926.1.4.1.3.2.2.0
Indicates the number of Battery strings that support
Health Analysis
Read Only Integer
atiBBSysAppsBattPerStringCount 1.3.6.1.4.1.926.1.4.1.3.2.3.0
Indicates the number of Batteries that support
Health Analysis
Read Only Integer
atiBBSysAppsBattConductanceMeasurementDate 1.3.6.1.4.1.926.1.4.1.3.2.4.0 Date of last conductance measurement Read Only Octet String Date and Time
atiBBSysAppsBattStandbyTimeRemaining 1.3.6.1.4.1.926.1.4.1.3.2.5.0
Remaining runtime if batteries are currently
discharging or available runtime for next discharge
Read Only Integer
1=overThreeHr
2=twoToThreeHr
3=oneToTwoHr
4=lessThanOneHr
5=calculating
6=notAvailable
10.1 Denitions and Settings, continued
10.0 Alpha MIB Parameters, continued