User Manual

78
746-257-B5-001, Rev. A1 (11/2013)
10.1 Denitions and Settings, continued
Parameter OID Description Access Type Value
ENVIRONMENTAL MANAGER
atiMgmtSysTempMgr 1.3.6.1.4.1.926.1.3.2.4.0 Object Identier
atiMgmtSysTempCtrl 1.3.6.1.4.1.926.1.3.2.4.1.0 Environmental Control Read/Write Integer 1=off (default)
2=OnTimer
3=OnTemp
4=onTimerTemp
5=on
atiMgmtSysTempStatus 1.3.6.1.4.1.926.1.3.2.4.2.0 Environmental Control Feedback State Read Only Integer 1=Contact Open (default)
2=Contact Closed
atiMgmtSysTempMode 1.3.6.1.4.1.926.1.3.2.4.3.0 Environmental Mode (Heat/Cool) Read/Write Integer 1=Heater (default)
2=Cooler
atiMgmtSysTempActiveState 1.3.6.1.4.1.926.1.3.2.4.4.0 Environmental Control Contact State
(Open/Closed)
Read/Write Integer 1=Closed (default)
2=Open
atiMgmtSysTempTemperature 1.3.6.1.4.1.926.1.3.2.4.5.0 Environment Temperature Read/Write Integer 1...70ºC
atiMgmtSysTempHysteresis 1.3.6.1.4.1.926.1.3.2.4.6.0 Environmental Temperature Hysteresis Read/Write Integer 1...10ºC
atiMgmtSysTempTimer 1.3.6.1.4.1.926.1.3.2.4.7.0 Environmental Default Timer Read/Write Integer 0...1440 (30 minute default, 15
minute increments)
atiMgmtSysTempCountdown 1.3.6.1.4.1.926.1.3.2.4.8.0 Environmental Timer Time Remaining Read Only Integer 0...1440 (in minutes)
atiMgmtSysTempStatusInvert 1.3.6.1.4.1.926.1.3.2.4.9.0 State Inverted to match the type of
relay operation on the heater mat
controller
Read/Write Integer 1=No invert (default)
2=Invert
GENERAL CONTROLS
atiMgmtSysTamperPolarity 1.3.6.1.4.1.926.1.3.2.6.1.0 Determines when tamper is active Read/Write Integer 1=Alarm On Open (default)
2=Alarm On Close
atiMgmtSysAlphaBusSize 1.3.6.1.4.1.926.1.3.2.6.2.0 Internal microprocessor
communications bus size. Alpha XM3
series power supplies use 9 bit. Alpha
GMX and VMX series supplies use 8 bit
Read/Write Integer 1=9 Bit (default)
2=8 Bit
atiMgmtSysBatteryCalMode 1.3.6.1.4.1.926.1.3.2.6.3.0 This parameter determines which of the
calibration tables to use in cases where
the battery negative is tied to ground or
when it oats.
Read/Write Integer 1=Float
2=Negative
atiMgmtSysAlphaBusSpeed 1.3.6.1.4.1.926.1.3.2.6.4.0 Select the speed at which the AlphaBus
will communicate
Read/Write Integer 1=baud9600
2=baud57600
atiMgmtSysGnrlInfoCongs 1.3.6.1.4.1.926.1.3.2.7.1 Object Identier
atiMgmtSysGnrlInfoCongsMain 1.3.6.1.4.1.926.1.3.2.7.1.1.0 An ASCII string programmed into the
main board non-volatile memory
Read Only Octet String Product number, conguration
number serial number, etc.
atiMgmtSysGnrlInfoCongsDaughter 1.3.6.1.4.1.926.1.3.2.7.1.2.0 An ASCII string programmed into the
C/D battery circuitry (IDH4X only)
Read Only Octet String Product number, conguration
number serial number, etc.
atiMgmtSysGnrlInfoCongsBase 1.3.6.1.4.1.926.1.3.2.7.1.3.0 An ASCII string describing the base
conguration of the device
Read Only Octet String i.e. IDH4, IDH4X
ENVIRONMENTAL CONTROL CONNECTOR
atiMgmtSysIO 1.3.6.1.4.1.926.1.3.2.8 Object Identier
atiMgmtSysIOSelect 1.3.6.1.4.1.926.1.3.2.8.1.0 Designates what function the ENV IO
pins are being used for.
Read/Write Integer 1=notInstalled(1)
2=lapOnly(2)
3=heaterControlOnly(3)
4=generatorOnly(4)
5=heaterControlAndLap(6)
6=generatorAndLap(6)
96=auxIO_1(96)
97=auxIO_2(97)
98=auxIO_3(98)
99=auxIO_4(99)
atiMgmtSysIOGenState 1.3.6.1.4.1.926.1.3.2.8.3.0 Current state of the generator when
the portable generator sense lines are
being used
Read only Integer 1=notInstalled
2=genOff
3=genRunning
4=genNotDetected
5=error
10.0 Alpha MIB Parameters, continued