6.0 Data Management, continued
Discrete Alarms Description Setting
psInverterStatus (1) Inverter OFF Disable
psInverterStatus (2) Inverter running due to loss of AC Line voltage discreteMinor
psInverterStatus (3) Self Test initiated locally Disable
psInverterStatus (4) Self Test initiated remotely Disable
psInverterStatus (5) Last Self Test failed discreteMajor
psMajorAlarm (1) No Alarm Disable
psMajorAlarm (2) Alarm discreteMajor
psMinorAlarm (1) No Alarm Disable
psMinorAlarm (2) Alarm discreteMinor
psTamper (1) Closed Disable
psTamper (2) Open discreteMajor
psInputVoltagePresence (1) AC Line Voltage Lost Disable
psInputVoltagePresence (2) AC Line Voltage Present Disable
tibControlMode (1) Device will respond to commands Disable
tibControlMode (2) Device is under local control Disable
tibControlMode (3) Remote device is not responding discreteMajor
Discrete Alarms for Optional Generator
genGeneratorStatus (1) Generator Off Disable
genGeneratorStatus (2) Generator Running (Test) discreteMinor
genGeneratorStatus (3) Generator Running discreteMajor
genGeneratorStatus (4) Generator Fail discreteMajor
genGasHazard (1) No Alarm Disable
genGasHazard (2) The concentration of hydrocarbon fuel in the generator enclosure has exceeded safe
limits. Generator operation is suspended. The alarm is cleared when the sensor reports
safe conditions, and the alarm is reset via the resetLatchedAlarms(3) command found in
the genEquipmentControl MIB point..
discreteMajor
genWaterIntrusion (1) No Alarm Disable
genWaterIntrusion (2) Water level within the generator or fuel enclosure has exceeded safe limits for generator
operation. Generator operation is suspended while this alarm is active. The alarm resets
when the water returns to a safe level.
discreteMajor
genPadShear (1) No Alarm Disable
genPadShear (2) Indicates that the generator or fuel enclosure has shifted from its mounting position.
Generator operation is suspended. The alarm resets when the unit is returned to its
original position.
discreteMajor
genEnclosureDoor (1) No Alarm Disable
genEnclosureDoor (2) Generator and/or auxiliary fuel enclosure door is open discreteMajor
genCharger (1) No Alarm Disable
genCharger (2) Ignition battery charger is not operating correctly discreteMajor
genFuel (1) No Alarm Disable
genFuel (2) Indicates the engine's fuel supply is insufcient for extended operation. Alarm resets
when fuel is replenished.
discreteMajor
genOil (1) No Alarm Disable
genOil (2) Indicates the engine's oil is inadequate for safe operation. Alarm resets when the
condition returns to normal.
discreteMajor
genMinorAlarm (1) No Alarm Disable
genMinorAlarm (2) The generator is indicating a minor alarm. The generator requires attention, but does not
require an immediate visit to the site.
discreteMinor
genMajorAlarm (1) No Alarm Disable
genMajorAlarm (2) The generator is indicating a major alarm. The generator requires immediate attention. discreteMajor
6.2.1 SCTE-HMS Congurable Alarms, continued
Table 6-4, Recommended Settings for Discrete Alarms