746-257-B2-001, Rev. B (01/2014)
12.0 Specications
Specifications for
AlphaNet IDH4 Family
IDH4X IDH4L
Power Supply Models Supported: XM2-HP, XM2 XM2-300HP
Battery Monitoring:
Up to four strings of 36 or 48V batteries (6V batts
congurable up to two strings)
One 12V battery (or two if AlphaCells)
Power System Management:
Up to ve power supplies and an AlphaGen generator
are managed from a single IDH4 Series including
coordinated battery charging, system test and
aggregated alarms
N/A
Management Protocol:
Standard ANSI/SCTE-HMS MIBs support basic power supply monitoring. Advanced diagnostics with
battery and power module analytics available via secure SNMP
Advanced Diagnostics
1
Intelligent Power Supply
Interface:
Power supply user interface displays advanced diagnostics including: DOCSIS modem upstream and
downstream RF levels, IP address assigned by network DHCP server, MAC address and rmware
versions, individual battery voltages to verify correct wire harness installation
Hardware
RF Cable Interface:
F-connector, female, 75 Ohm, connector angle better accommodates coax bend radius when installed in
some enclosures
Local Interface: RJ-45, Ethernet, 10/100Mbps
LED Indicators:
Ready/Alarm, Upstream registration, Downstream lock, AlphaBus activity, RF level, Link, CPE trafc, Battery
Sense harness correctly connected
I/O Control
(IDH4X and IDH4L
Only)
:
6-pin Molex: Digital input, Digital output, 5V, Common
AlphaBus: RJ-11 offset tab: Multiple-power supply and AlphaGen communications
Battery Monitoring:
8-pin Molex battery string A/B and 8-pin Molex battery
string C/D.
N/A
Tamper: NO or NC, software congurable, reads enclosure door magnetic switch
Environment
Operating Temperature: -40 to 65°C / -40 to 149°F
Storage Temperature: -40 to 85°C / -40 to 185°F
Humidity: 10 to 90% non-condensing
Regulatory Compliance:
FCC Part 15 Class A
EN 50083-2:2006 EMC requirements for CATV equipment
EN 62040-2:2006 Uninterruptable power supply EMC requirements, Category C2
Surge: IEEE 587, Category B3
RoHS: Directive 2002/95/EC
1
Advanced diagnostics are available through Alpha Certied network monitoring systems
Network Communications
DOCSIS (RF) Port Protocols: IP, UDP, TCP, DHCP, TFTP, SNMPv1,SNMPv2c, HTTP, SNTP
Ethernet Port:
Local Mode: HTTP Web interface for local on-site diagnosis.
CPE Mode: DOCSIS Cable modem Ethernet CPE functionality
MIBs:
Power supply (ANSI/SCTE 38-4)
Other SCTE-HMS MIBs as dened by the SCTE for power supply and generator status monitoring
Alpha proprietary advanced UPS diagnostics