Instruction Manual
38 745-814-B0-001, Rev. A
6.0 Data Management, continued
6.3 SCTE-HMS MIB Alarms, continued
6.3.1 SCTE-HMSCongurableAlarms,continued
DiscreteAlarmDenitionsandCommonSettings
Discrete Alarms Discrete Alarm
Value
Denition Example
Settings
psInverterStatus 1 Inverter is off Disable
psInverterStatus 2 AC Input line loss EnableMinor
psInverterStatus 3 Inverter is in a local test cycle Disable
psInverterStatus 4 Remote inverter test has been
initiated
Disable
psInverterStatus 5 The last Inverter test failed. EnableMinor
psMajorAlarm 1 No alarm Disable
psMajorAlarm 2 Service has been dropped or a
service interruption is imminent. This
is a general alarm; the cause of which
can be determined by looking in the
Discretes Table.
EnableMajor
psMinorAlarm 1 No alarm Disable
psMinorAlarm 2 A non-service effecting condition has
occurred and should be monitored
EnableMinor
psTamper 1 Indicates status of enclosure door
tamper sensor: closed (door is open).
EnableMinor
psTamper 2 Indicates status of enclosure door
tamper sensor: open (door is closed).
Disable
psInputVoltagePresence 1 Digital value indicating that
line voltage is lost, based on
measurement of input voltage.
EnableMinor
psInputVoltagePresence 2 Indicates that line voltage is present
and within tolerance, based on
measurement of input voltage.
Disable
transponderInterfaceBusIdent 1 Remote device will respond to
commands from master transponder.
Disable
transponderInterfaceBusIdent 2 Local device is under local control and
will not respond to commands from
master transponder.
EnableMinor
transponderInterfaceBusIdent 3 Device is not responding. EnableMajor
Table 6-5, Discrete Alarm Denitions and Common Settings