6.0 Data Management, continued
6.3 SCTE-HMS MIB Alarms, continued
6.3.1 SCTE-HMSCongurableAlarms,continued
Example:
The alarms for psTemperature below are set so that the normal temperature range
is from 30°C to 45°C. If the temperature rises above 45°C, a casHI alarm will be
sent to the alarmTable. Anything over 50°C is considered a critical condition and
will generate a casHIHI alarm. If the temperature falls below the normal level of
30 degrees, and casLO will be generated, and if it continues to drop below 0, a
casLOLO will be generated. The temperature must rise above the LOLO limit plus
the deadband value of 3°C before the casLOLO alarm will change to a casLO. The
alarmEnable eld is set to 0F Hex to monitor and alarm for all conditions.
Binary to Hex Conversions for Alarm Settings
Unused HiHi Hi Lo LoLo Hex Enabled Alarms
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0 0 0 0 0 00 No Alarms
0 0 0 0 0 0 0 1 01 LoLo
0 0 0 0 0 0 1 0 02 Lo
0 0 0 0 0 0 1 1 03 Lo, LoLo
0 0 0 0 0 1 0 0 04 Hi
0 0 0 0 0 1 0 1 05 Hi, LoLo
0 0 0 0 0 1 1 0 06 Hi, Lo
0 0 0 0 0 1 1 1 07 Hi, Lo, LoLo
0 0 0 0 1 0 0 0 08 HiHI
0 0 0 0 1 0 0 1 09 HiHi, LoLo
0 0 0 0 1 0 1 0 0A HiHi, Lo
0 0 0 0 1 0 1 1 0B HiHi, Lo, LoLo
0 0 0 0 1 1 0 0 0C HiHi, Hi
0 0 0 0 1 1 0 1 0D HiHi, Hi, LoLo
0 0 0 0 1 1 1 0 0E HiHi, Hi, Lo
0 0 0 0 1 1 1 1 0F HiHi, Hi, Lo, LoLo
Table 6-3, Binary to Hex Conversions for Alarm Settings
psTemerature