Installation and Operation Manual Owner manual
745-020-B0-003, Rev. C
33
3.0 Installation, continued
3.7 Connecting the DC Output Connection
1. Locate and remove the safety shroud. The shroud is held in place with two thumbscrews.
Shroud Location
2. Strip the user-supplied DC load wires 3/4". Loosen the 3/16" Allen screws and insert the
DC load wires. Torque to 120 in-lbs and replace the safety shroud.
Negative DC
Load Connection
Fig. 3-8, DC Output Safety Shroud
Fig, 3-9, DC Output Block
Positive DC
Load Connection