1.4 Specifi cations
System Specifi cations Specifi cation
System Size Height: 39.0" (57" with optional pedestal)
Width: 39.25"
Depth: 24"
Weight: 338 lbs (370 lbs with optional pedestal)
Acoustic 70.3 dBa @ 10 feet, (100% load)
DC Electrical Noise (PN-6x-T) RF: <100mV RMS in any 3kHz Band, 3kHz to
20MHz
Broadband: <250mV Pk to Pk
Voice Freq. Noise: Less than 56dBnrc
Gas Inlet Pressure 0.5-2 psi NOTE: Contact Alpha Technologies for
low pressure operation below 0.5 psi.
Integral Ignition Battery Charger Voltage 13.5 to 14.3VDC regulated, 15A max,
Remote Interface Length 12’ max. (sweep to sweep)
NOTE: Distance depends upon proper installation,
derating, and wire gauge. Contact Alpha Technolo-
gies for installations requiring greater distances.
Agency Compliance UL 1778, UL2200, CSA 22.2 No. 107.1, and appli-
cable sections of NFPA 37/54/58 and 70, EMC/FFC
Part 15 Class A
Exterior Surface Temperature 70°C max. (meets requirements of UL/CSA)
Fuel System Controls & Monitoring The controls and fuel system meet appropriate
sections of NFPA 37,54, and 58 for automatic,
unattended remote operation of enclosed
generators.
Sensors Gas Hazard, Pad Shear, Water Intrusion, Tamper,
Low Fuel Pressure
Safety Shutdowns Low oil shutdown
Oil over-temp
Engine over-speed
Over-crank (Crank limit)
Gas hazard (LPG or natural gas)
Low fuel pressure shutdown (LPG)
Water intrusion
Pad shear
Alternator over-voltage