4.3.9 ECM-PWR GRI Enclosure Sensor Interface Ribbon Cable
The connector is a 14 pin 0.100 spaced, 150V rated ribbon cable with
polarized cable connectors that prevent incorrect connections in the field.
Designations for the connector mounted on the PCBA shall be identified by silk
screen J1 and marked with the #1 pin of the PCB receptacle for polarization.
See Fig. 4-9 for location.
Pin Description
1 Low Oil Pressure*
2 Over-Temp*
3 Over-Speed*
4 Over-Crank*
5 Engine Run*
6 Over Voltage Shutdown*
7 Alternator Output Active (ON)* (Developed by Charger Circuit)
8 Switch Not In Auto* (Auto-Off-Manual switch control switch)
9 Low Ignition Battery*
10 Logic Common - all alarms listed above
11 Control RTY* (Relay Transfer Switch low = Generator AC power) (Referenced
to pin 13)
12 Start* and Engine Run Enable* (See below) (Also remote test from external
test routine)
13 Start/Stop Power Common
14 Stop* (To Stop APU after test is complete)
Note: Active low determined by (*) symbol.
Note: The Pin #12 serves two functions:
-Collocated operation with ACU, START* command causes the engine
to latch on and continue to run when START* is released.
-Remote operation with ECM, ENGINE RUN ENABLE* (Pin 12)
command enables the engine to run as long as the signal is held
active LOW, and shuts down when the ENGINE RUN ENABLE* is
released.
(1*,1(
4.3 Connectors, continued
Fig.4-10 ECM-PWR GRI Enclosure Sensor Interface Ribbon Cable