Manual

9
745-680-B9-001
3.0 Speci cations, continued
3.1 General Speci cations
Model
Rated
Voltage
Rated Capacity (Ah) Dimensions (in/mm)
Number
of Poles
Weight
(lb./Kg)
10hr. to
1.80Vpc (C
10
)
3hr. to
1.80Vpc (C
3
)
1hr. to
1.80Vpc (C
1
)
Length Width Height
SMU 2-
200-FR
2 200 150 110 4.25/120 8/200 15/385 2 35/16
SMU 2-
300-FR
2 300 225 165 6/161 8/200 15/385 2 50/23
SMU 2-
400-FR
2 400 300 220 8/201 8/200 15/385 2 66/30
SMU2
-500-FR
2 500 375 275 9.5/242 8/200 15/385 2 84/38
SMU 2-
600-FR
2 600 450 330 11/283 8/200 15/385 4 99/45
SMU 2-
800-FR
2 800 600 440 7/183 9.5/244 24.5/629 4 136/62
SMU 2-
1000-FR
2 1000 750 550 8.5/218 9.5/244 24.5/629 4 167/76
SMU 2-
1500-FR
2 1500 1125 825 12/305 9.5/244 24.5/629 6 244/111
SMU 2-
2000-FR
2 2000 1500 1100 14.5/369 9/228 24.25/617 8 337/153
3.2 Battery Internal Resistance
Battery internal resistance is a nonlinear parameter that changes with changes in battery
temperature and discharge state. The internal resistance is lowest when the battery is fully
charged. At full charge and 25°C the internal resistances and short circuit currents are as
follows:
Table 3-1, General Speci cations
Model Internal Resistance (m Ω) Short Circuit Current (A)
SMU 2-200-FR 0.514 3940
SMU 2-300-FR 0.363 5588
SMU 2-400-FR 0.297 6816
SMU2 -500-FR 0.218 9361
SMU 2-600-FR 0.175 11576
SMU 2-800-FR 0.223 9153
SMU 2-1000-FR 0.189 10804
SMU 2-1500-FR 0.152 13237
SMU 2-2000-FR 0.115 17391
Table 3-2, Internal Resistance and Short Circuit Current (25°C)
A short circuit will drop the battery voltage to zero and physically damage its internal components,
poles, and connectors.
CAUTION!