14.0 Speci cations, continued
Battery Water Quality Maximum Impurities (Parts per Million (PPM))
Requirements Maximum Allowable Limits
Total Solids 350.0
Fixed Solids 200.0
Organic and Volatile 150.0
Iron 4.0
Chloride 25.0
Ammonium (NH4) 4.0
Nitrates (NO2) 10.0
Nitrates (NO3) 10.0
Manganese 0.07
Calcium and Magnesium 40.0
Table 14-9, Demineralized Water Impurities «
List of Reference Standards
Stationary lead-acid batteries. General requirements and methods of test Part 1. Vented types. EN60896-1, IEC 896-1
Sulphuric acid for use in lead-acid batteries BS3031
Sulphuric acid and water for use in lead-acid batteries DIN 43 530-1
Stationary lead-acid batteries accessories DIN 40 740
Stationary lead-acid batteries - tubular positive plates DIN 40 736
Safe operation of starter batteries BS 6604
Safety reqs for secondary batteries and battery installations Part 2: Stationary lead-acid batteries EN50 272-2 (VDE 0510)
Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-Acid
Batteries for Stationary Applications
IEEE 450
Recommended practice fro installation design and installation of vented lead-acid batteries for
stationary applications (ANSI/BCI)
IEEE 484
Sizing lead-acid batteries for stationary applications (BCI) IEEE 485
Table 14-10, List of Reference Standards «