Specifications
31
We reserve the right to modify technical specifications without prior notice.
UK830301/170306 © Alpha-InnoTec GmbH
Gerätebezeichnung
Heat pump type Brine/water ı Air/water ı Water/water • applicable ı — not applicable
Installation location Indoors ı Outdoors • applicable ı — not applicable
Conformity CE
Performance data Heating capacity/COP at
B0/W35 Standard point acc. to EN14511
2 condensers
1 condensers
kW ı …
kW ı …
B0/W45 Standard point acc. to EN14511 kW ı …
B0/W35 Standard point acc. to EN255
2 condensers
1 condensers
kW ı …
kW ı …
Limits of application Heating circuit °C
Heat source °C
Additional operating points …
Sound Sound level measured at distance of 1m around the device (in reverberating room) dB(A)
Sound power level according to EN12102 dB
Heat source Volume ow: minimum ow rate ı nominal ow rate ı maximum ow rate l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı volume ow bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı volume ow bar (bar) ı l/h
Anti-freeze agent monoethylene glycol
minimum concentration ı frost proof down to % ı °C
Heating circuit Volume ow: minimum ow rate ı nominal ow rate ı maximum ow rate l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı volume ow bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı volume ow bar (bar) ı l/h
General unit data Dimensions (see dimensional drawing for the specied unit size) unit size
Total weight (including cooling) kg (kg)
Additional weight module 1 kg
Additional weight module 2 kg
Connections Heating circuit …
Heat source …
Refrigerant Refrigerant type ı Quantity … ı kg
Hot water tank Net contents l
External current anode integrated
Hot water temperature up to °C
Output 38°C | 45 °C at removal of 10 l/min l ı l
Electric Voltage code ı all-pole circuit breaker heat pump *) … ı A
Voltage code ı circuit breaker control voltage *) … ı A
Voltage code ı circuit breaker electric heating element *) ı A
Heat Pump Effective power consumption in standard point B0/W35 according to EN14511: Power consumption ı current consumption ı cosφ kW ı A ı …
Maximum device current within the limits of application A
Starting current: direct ı with soft starter A ı A
Protection type IP
Output electric heating element 3 ı 2 ı 1 phase kW ı kW ı kW
Components Circulating pump heating circuit at nominal ow rate: Power consumption ı current consumption kW ı A
Circulating pump heat source at nominal ow rate: Power consumption ı current consumption kW ı A
Passive cooling function Specication only for units with designator K: Cooling output at nominal volume ow (15 °C heat source, 25 °C heating water) kW
Safety equipment Safety component heating circuit ı Safety component heat source Includ. in scope of delivery: • yes
Heating and heat pump regulator Includ. in scope of delivery: • yes — no
Electronic soft starter integrated: • yes — no
Expansion vessels Heat source: Scope of delivery ı Volume ı Initial pressure • yes — no ı l ı bar
Heating circuit: Scope of delivery ı Volume ı Initial pressure • yes — no ı l ı bar
Overow valve integrated: • yes — no
Vibration decouplers Heating circuit ı heat source Included in scope of delivery: • yes — no
UK813195 *) comply with local regulations n.n. = not detectable
WZS 100H(/K)
• ı — ı —
• ı —
•
—
10,2 ı 4,6
—
—
10,3 ı 4,7
20 – 65
-5 – 25
—
37
49
1400 ı 2200 ı 3500
— ı —
0,42 (0,39) ı 1600
•
25 ı -13
900 ı 1800 ı 2200
— ı —
0,35 (0,31) ı 1300
1
310 (317)
215
95
R1"AG
G1" ÜWM DIN ISO 228
R407c ı 2,1
200
•
55°
250 ı 210
3~/PE/400V/50Hz ı C10
1~/N/PE/230V/50Hz ı B10
3~/N/PE/400V/50Hz ı C10
2,2 ı 4,4 ı 0,73
6,9
— ı 20
20
6 ı 4 ı 2
0,08 ı n.n.
0,1 ı n.n.
8,3
• ı •
•
•
• ı 12 ı 0,5
• ı 25 ı 1,5
•
• ı •
813168-c
WZS 80H(/K)
• ı — ı —
• ı —
•
—
8,4 ı 4,4
—
—
8,6 ı 4,6
20 – 65
-5 – 25
—
37
49
1200 ı 1800 ı 3000
— ı —
0,37 (0,35) ı 1400
•
25 ı -13
750 ı 1400 ı 1800
— ı —
0,35 (0,33) ı 1000
1
305 (312)
215
90
R1"AG
G1" ÜWM DIN ISO 228
R407c ı 2,0
200
•
55°
250 ı 210
3~/PE/400V/50Hz ı C10
1~/N/PE/230V/50Hz ı B10
3~/N/PE/400V/50Hz ı C10
1,91 ı 3,8 ı 0,73
5,9
30,0 ı —
20
6 ı 4 ı 2
0,08 ı n.n.
0,1 ı n.n.
6,8
• ı •
•
—
• ı 12 ı 0,5
• ı 25 ı 1,5
•
• ı •
813167-d
WZS 60H(/K)
• ı — ı —
• ı —
•
—
5,7 ı 4,4
—
—
5,8 ı 4,7
20 – 65
-5 – 25
—
37
49
900 ı 1400 ı 2800
— ı —
0,4 (0,38) ı 1100
•
25 ı -13
500 ı 950 ı 1200
— ı —
0,43 (0,42) ı 700
1
300 (307)
215
85
R1"AG
G1" ÜWM DIN ISO 228
R407c ı 1,65
200
•
55°
250 ı 210
3~/PE/400V/50Hz ı C10
1~/N/PE/230V/50Hz ı B10
3~/N/PE/400V/50Hz ı C10
1,30 ı 2,5 ı 0,75
4
27,0 ı —
20
6 ı 4 ı 2
0,08 ı n.n.
0,1 ı n.n.
5,8
• ı •
•
—
• ı 12 ı 0,5
• ı 25 ı 1,5
•
• ı •
813166-c