Specifications

23
Model designation
Heat pump type Brine/water ı Air/water ı Water/water applicable ı not applicable
Installation location Indoors ı Outdoors applicable ı not applicable
Conformity CE
Performance data Heating capacity/COP heat optimised at
A7/W35 Standard point acc. to EN14511 1 compressor kW ı
A7/W45 Standard point acc. to EN14511 1 compressor kW ı
A2/W35 Operating point acc. to EN14511 1 compressor kW ı
A10/ W35 Operating point acc. to EN14511 1 compressor kW ı
A-7/ W35 Operating point acc. to EN14511 1 compressor kW ı
Performance data Cooling capacity/EER cool optimised at
A27/ W18 Operating point acc. to EN14511 1 compressor kW ı
A27/ W7 Operating point acc. to EN14511 1 compressor kW ı
A35/W18 Operating point acc. to EN14511 1 compressor kW ı
A35/W7 Operating point acc. to EN14511 1 compressor kW ı
Heating limits Heating circuit (water) °C
of application Heat source (air) °C
Additional operating points °C
Cooling limits Cooling circuit (water) °C
of application Heat sink (air) °C
Sound Sound pressure level outside (measured at distance of 1m around air connections) dB(A)
Sound pressure level outside (measured at distance of 1m around air connections) dB(A)
Heat transfer Air volume flow at maximum external compression m³/h
medium air Maximum external pressure Pa
Heat transfer Volume flow: minimum flow rate ı nominal flow rate A7/W35 EN14511 ı maximum flow rate l/h
medium water Pressure losses heating/cooling ∆p ı volume flow bar ı l/h
Pressure losses hot water circuit/swimming pool circuit ∆p ı volume flow bar ı l/h
General unit data Dimensions (see dimensional drawing for the specified unit size) unit size
Total weight kg
Connections Heating circuit / cooling circuit
Hot water circuit / swimming pool circuit
Refrigerant Refrigerant type ı Quantity ı kg
Free cross section, air channels mm
Cross section, condensate water / length from unit mm ı m
Elektric Voltage code ı all-pole circuit breaker heat pump **) ı A
Voltage code ı circuit breaker control voltage **) ı A
Voltage code ı circuit breaker electric heating element **) ı A
Heat pump Effect. power consumption in standard point A7/W35 acc. to EN14511: Power consumption ı current consumption ı cosφ kW ı A ı
Maximum device current within the limits of application A
Starting current: direct ı with soft starter A ı A
Protection type IP
Output electric heating element 3 ı 2 ı 1 phase kW ı kW ı kW
Safety equipment Safety component heating circuit ı Safety component heat source Incl. in scope of delivery: yes no
Heating and heat pump regulator Included in scope of delivery: yes no
Control and sensor wire Included in scope of delivery: yes no
Power cable to unit Included in scope of delivery: yes no
Electronic soft starter integrated: • yes no
Expansion vessels Heating circuit: Scope of delivery ı Volume ı Initial pressure yes no ı l ı bar
Overflow valve integrated: • yes no
Vibration decouplers Heating circuit Included in scope of delivery: yes no
UK813506c
*) depending on components tolerances and flow **) comply with local regulations n.n. = not detectable w.w. = optional
¹) hot water return flow ²) hot water forward flow
LW 140 A/RX
ı ı
ı
14,4 ı 4,2
13,9 ı 3,5
13,8 ı 3,5
14,1 ı 4,3
10,8 ı 2,9
20,3 ı 3,8
15,4 ı 3,2
18,4 ı 2,9
14,2 ı 2,5
20¹ 52²
-20 40
A> -7 / 6
20²
15 40
56
5100
2000 ı 3000 ı 3750
0,024 ı 2100
ı
4
280
R5/4”AG
R407C ı 10,2
30 ı 1
3~/PE/400V/50Hz ı C16
1~/N/PE/230V/50Hz ı B10
3,95 ı 7,6 ı 0,75
11,9
74 ı 30
24
813506d
LW 90 A/RX
ı ı
ı
9,2 ı 4,1
8,9 ı 3,3
9,4 ı 3,5
9,7 ı 4,3
7,2 ı 2,8
14,5 ı 3,7
10,8 ı 3,2
13,0 ı 2,9
9,9 ı 2,5
20¹ 52²
-20 40
A> -7 / 6
20²
15 40
55
4000
1350 ı 2000 ı 2500
0,031 ı 1450
ı
2
260
R 1"AG
R407C ı 6,8
30 ı 1
3~/PE/400V/50Hz ı C10
1~/N/PE/230V/50Hz ı B10
2,25 ı 4,3 ı 0,75
8,1
51,5 ı 30
24
813505a
We reserve the right to modify technical specifications without prior notice.
83051400aUK © Alpha-InnoTec GmbH