Technical data

4
2.7 FLUE LENGTHS
Flue length = 0.75 m (not including the terminal, which is supplied with the boiler)
Note: Additional flues (of the same length) are available.
Length of Flue Required:-
Rear Flue = wall thickness +115 mm
Side Flue = wall thickness + distance between wall and side of boiler + X mm (L/H side X = 380, R/H side X = 130)
Vertical Flue = distance from top of boiler side panel to required roof position minus 1 m for vertical terminal assembly
Maximum flue length = 4 m horizontal or 4 m vertical.
Each additional 90° Bend is equivalent to 1 m of flue length.
Each 45° Bend is equivalent to 0.5 m of flue length.
The Vertical Flue terminal assembly is equivalent to 1 m of flue length.
Alpha 500E - Technical Data
2.8 AVAILABLE PUMP HEAD FOR CENTRAL HEATING
gal/min
4.1
3.4
2.78
2.32
1.86
1.65
Btu/h
95563
80 000
60 000
50 000
40 000
35 495
metres
1.0
2.2
3.6
4.2
4.8
5.0
feet
3.28
7.22
11.8
13.7
15.7
16.4
Output Available pump head
metres
2.1
3.4
4.2
4.6
5.1
5.3
feet
6.9
11.1
13.7
15.1
16.7
17.3
metres
3.5
2.6
1.6
1.2
0.9
0.8
feet
11.5
8.5
5.2
3.9
2.9
2.6
metres
2.7
1.8
1.2
1.0
0.7
0.6
feet
8.9
5.9
3.9
3.3
2.3
2.0
Pressure loss across boiler
gal/min
4.8
4.0
3.27
2.73
2.18
1.94
litre/min
18.4
15.2
12.60
10.50
8.40
7.45
17°C 20°C
litre/min
21.7
18.3
14.82
12.35
9.88
8.77
17°C 20°C 17°C 20°C
Flow rate
kW
28.00
23.44
17.58
14.65
11.72
10.40
1. Ensure wires are connected
correctly
2. Only fit the Alpha recommended
clock. Other clocks could cause
damage.
WARNING
Blue
Wire
Brown
Wire
Black
Wire
12345
Internal Clock Terminals
Black
Wire
Not
Used
Clock connections
2.9 ELECTRICAL CONNECTIONS
Note: This Appliance Must Be Earthed
An optional integral Clock kit is available if required.
Boiler terminal block
Fig. 1
This information is based on 17°C and 20°C system design temperature difference.