Technical Specifications

ICC-ES Evaluation Report ESR-1668 FBC Supplement
Reissued October 2017
This report is subject to renewal October 2018.
www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council
®
DIVISION: 07 00 00THERMAL AND MOISTURE PROTECTION
Section: 07 46 46Fiber-Cement Siding
REPORT HOLDER:
PLYCEM USA, INC.
FIBER CEMENT PRODUCTS
15055 WOODHAM DRIVE
HOUSTON, TEXAS 77073
(281) 742-7074
www.allurausa.com
EVALUATION SUBJECT:
ALLURA
FIBER CEMENT LAP SIDING, VERTICAL PANEL SIDING, SOFFIT PANELS AND SHAPES SIDING
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that Allura
Fiber Cement lap siding, vertical panel siding,
soffit panels and shapes siding, recognized in ICC-ES master evaluation report ESR-1668, have also been evaluated for
compliance with the codes noted below.
Applicable code editions:
2010 Florida Building CodeBuilding
2010 Florida Building CodeResidential
2.0 CONCLUSIONS
The Allura
products, described in Sections 2.0 through 7.0 of the master evaluation report ESR-1668, comply with the 2010
Florida Building CodeBuilding and the 2010 Florida Building CodeResidential, provided the design and installation are in
accordance with the International Building Code
®
provisions noted in the master report and the following conditions apply.
Design wind loads must be based on Section 1609 of the 2010 Florida Building CodeBuilding or Section 301.2.1.1 of
the 2010 Florida Building CodeResidential, as applicable.
Load combinations must be in accordance with Section 1605.2 or Section 1605.3 of the 2010 Florida Building Code
Building, as applicable.
Siding attachment must meet the requirements of Section R703.4 of the 2010 Florida Building CodeResidential, where
applicable.
Use of the Allura
for compliance with the High-Velocity Hurricane Zone provisions of the 2010 Florida Building Code
Building and the 2010 Florida Building CodeResidential has not been evaluated, and is outside the scope of this
supplemental report.
For products falling under Florida Rule 9N-3, verification that the report holder’s quality assurance program is audited by a
quality assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the
responsibility of an approved validation entity (or the code official when the report holder does not possess an approval by
the Commission).
This supplement expires concurrently with the master report, reissued October 2017.
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
Copyright © 2017 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 1