Owner`s manual

12
CONNECTING A VEHICLE DETECTOR TO THE
RS1000
For a REVERSING LOOP connection of the vehicle detector, the
"relay" or "presence" output of the detector will be connected to
Terminal #11 (REV LOOP) of the RS1000 and the COMMON wire will
be connected to Terminal #0 or #16 (COMMON) of the RS1000. As
long as a relay closure is present on these two lines, the RS1000 will not
allow the gate to close. If the gate is opening, the gate will continue to
open. If the signal is removed before the Timer to Close times out, the
gate will close after the Timer to Close has completed its cycle.
For a FREE EXIT connection of a Vehicle Detector, the RELAY or
PRESENCE output signal will be connected to Terminal #5 (FREE
EXIT) and the RELAY COMMON signal connected to Terminal #0 or
#16 (COMMON) of the RS1000. DO NOT CONNECT THE FREE
EXIT OUTPUT SIGNAL TO ANY OTHER TERMINAL, SUCH AS
RADIO RELAY, BECAUSE THE GATE WILL
CLOSE AFTER
REACHING THE OPEN LIMIT AND THE TIMER TO CLOSE HAS
COMPLETED ITS CYCLE, EVEN THOUGH THE VEHICLE HAS
NOT EXITED THE FREE EXIT LOOP.
FINAL INSTALLATION CHECKLIST
1. Use a voltmeter to assure the service voltage to the
operator is 115 VAC. Connection to 220 VAC service is
the most common cause of board failure in new
installations and is NOT COVERED BY WARRANTY!
2. No accessory equipment is installed in the control box.
3. All wires attached to the 3 or 6 position terminal strip are
well clear of the moving parts under the unit cover.
4. The junction box cover is securely fastened .
C: INSTALLING THE OPERATOR
# NAME
DESCRIPTION
0 COMMON
Common connection for low voltage
signal inputs, terminals 2 thru 15.
1 24 VAC
Provides maximum 10 VA auxiliary
power for accessories.
2 ALTERNATE
Momentary input, must be released
and re-entered to be recognized.
This input is used for “COMMAND OPEN/COMMAND
CLOSE” applications. The 1st signal will cause the gate to
begin opening. A 2nd signal received during the open cycle
will stop the gate immediately. A 3rd signal will close the gate.
Connect appropriate access control devices to this terminal
and #0 or #16 COMMON.
3 24 VAC
Provides maximum 10 VA auxiliary
power for accessories.
4 RADIO OPEN
Momentary input, must be released
and re-entered to be recognized.
Once activated the gate will open fully. Activation while the
gate is closing will cause it to re-open.
5 FREE EXIT
Momentary or continuous input.
Once activated the gate will open fully. Activation while the
gate is closing will cause it to re-open. Continuous activation
while the gate is open will prevent the Timer-To-Close function
from automatically closing the gate.
6 OPEN
Momentary or continuous signal. On/
Off mode set by Switch #1
Once activated the gate will open fully. Activation while the
gate is closing will cause it to re-open. Continuous activation
while the gate is open will prevent the Timer-To-Close function
from automatically closing the gate. Continuous signal
required to move the gate when in the alarm mode.
7 CLOSE
Momentary or continuous signal. On/
Off mode set by Switch #1
Once activated the gate will close fully. Activation while the
gate is opening has no effect. Continuous signal required to
move the gate when in the alarm mode.
TERMINAL STRIP REFERENCE CHART
# NAME
DESCRIPTION
8 STOP
Momentary or continuous signal.
Overrides all other signals. Once activated, the gate will
immediately stop and await a new command. If the STOP
input is continuously activated, the gate will not move.
9 OPEN PHOTO
Momentary or continuous signal.
This input is active only when referenced to the opening
direction, it has no effect on the gate when closing or about to
close. If activated when the gate is opening the gate will stop,
pause and reverse in the close direction for 1/2 second
(approx. 2 inches) and stop. Continuous activation will
prevent the gate from moving in the open direction. When the
input is removed normal operation is resumed. This input is
intended for photoelectric eye systems and other non-contact
devices as appropriate. Connect here and to terminal #16
COMMON. Multiple devices may be connected in parallel.
10 CLOSE PHOTO
Momentary or continuous signal.
This input is active only when referenced to the closing
direction, it has no effect on the gate when opening or about to
open. If activated when the gate is closing the gate will stop,
pause and reverse in the open direction for 1/2 second
(approx. 2 inches) and stop. Continuous activation will
prevent the gate from moving in the close direction. When the
input is removed normal operation is resumed. Continuous
activation while the gate is open will prevent the Timer-To-
Close function (if enabled) from automatically closing the gate.
This input is intended for photoelectric eye systems and other
non-contact devices as appropriate. Connect here and to
terminal #16 COMMON. Multiple devices may be connected
11 REV LOOP
Momentary or continuous signal.
This input is active only when the gate is closing or when it’s
fully open and the Close Timer is operative. All stand-alone
vehicle detectors, photo-eyes and active edges should be
connected here and to terminals #3 or #13 COMMON.
Multiple devices may be connected in parallel.